Draft v1.0 prepared by NEER. Not adopted by the Government of Andhra Pradesh or the Government of Puducherry (for Yanam), and has no legal force. About this draft

Andhra Pradesh · Draft v1.0

Andhra Pradesh Stormwater Design Manual

About this draft

Status. This is Draft v1.0 of the Andhra Pradesh Stormwater Design Manual. It was prepared by Neer as a proposed stormwater design standard for Andhra Pradesh.

Not adopted. This Manual has not been adopted, notified or endorsed by the Government of Andhra Pradesh or by any of its departments, local bodies or agencies. Where it names a body, such as MA&UD, DTCP, the Water Resources Department, APSDMA, APCRDA or a local body, it describes the role that body would have if the Manual were adopted. It does not say the body has agreed to that role.

Supplements. The Manual carries one supplement, for a place that lies within Andhra Pradesh but outside the State's jurisdiction. Supplement S01 covers Yanam, a town on the Godavari, surrounded by Andhra Pradesh, that is part of the Union Territory of Puducherry; it has not been adopted, notified or endorsed by the Government of Puducherry. What this notice says of the Manual applies to the supplement.

No legal force. Until a competent authority adopts it, with or without changes, this Manual has no legal force. The development rules, drainage standards and approval conditions in force continue to apply.

Use with care. Clauses and values may change after review. Designers remain responsible for their designs and for checking the data they use. Neer accepts no liability for decisions made on the basis of this draft.

Disclosure. Neer publishes the India Flood Atlas, a national map of modelled 1% AEP flood depth. Clause 6.11.3 names it as one example of a regional map that an Approving Authority may adopt for floor levels. The Manual does not require the Atlas; any map adopted under Clause 7.3.4 may be used.

Comments. Comments and corrections are welcome at info@neer.ai.

Preface

Andhra Pradesh's cities and towns flood for three reasons. The Vijayawada flood of September 2024 showed all three at once, and the cyclones that cross the coast each October and November show them again in town after town.

  1. Inadequate drain capacity. Drains are too small for the rain they receive, and many are narrower than they were built. About 125 mm fell over Vijayawada's urban mandals in some nine and a half hours on 31 August 2024, as reported from the State's mandal gauges. A storm water drainage programme sanctioned for the city in 2016 was left part-built, and in 2025 an outfall drain to the Krishna was found narrowed by encroachment from 10 ft to 2 ft. Roofs, roads and paving now send more water to the drains, and faster.
  2. Lost storage. Andhra Pradesh is a tank State: the first national Census of Water Bodies counted over 1.1 lakh tanks (cheruvulu and kuntas). Many that once held storm water have been filled or built over. The Census recorded 3,920 encroached water bodies in the State. Of 74 tanks test-checked by the Comptroller and Auditor General in six towns, 34 were encroached and 5, including Gunadala and Nalla Cheruvu in Vijayawada, had vanished. Kolleru lake, which receives the Budameru and the delta drains, was largely cut up into fish tanks before the demolitions of 2006. The water these tanks and wetlands used to store now runs into streets and homes.
  3. Blocked outfalls. Drains empty into the sea, the rivers, the delta drains and Kolleru. When the Krishna or the Godavari is in flood, or a cyclone raises the sea, the outfall closes, water backs up, and even a well-sized drain cannot empty. In September 2024 the Budameru breached its banks into Vijayawada while the Krishna stood at a record flow at Prakasam Barrage. Kolleru reaches the sea through a single channel, the Upputeru. In 2014 Cyclone Hudhud raised the sea about 1.4 m above the tide at Visakhapatnam port.

Two further hazards sit alongside these. Tank cascades can fail in sequence: in November 2021 heavy rain in Rayalaseema and the south coast breached about 125 tanks and bunds, and the Annamayya dam failed. And the cyclone season brings wind, rain and storm surge together, often with tanks already full and soils wet.

National guidance sizes public drains but does not control the runoff that new building adds. This Manual makes stormwater a condition of development approval. Every development above a modest size must:

  • hold frequent rainfall on site;
  • release the large storms no faster than the undeveloped land did, or slower where catchments already flood; and
  • show that its outfall still works when the tide or the river is high.

The Manual also sets how public drains, roads, canals, cheruvulu and basin-wide master plans are designed, so that private sites and public works aim at the same standard.

The Manual draws on leading stormwater standards from India and abroad. Each is adapted to Andhra Pradesh's two monsoons and its October–December cyclones, its tank cascades and surplus weirs, its red and black cotton soils, the Godavari and Krishna deltas with their drains and tidal outfalls, Kolleru, the hill streams of Visakhapatnam, saline coastal aquifers and high delta water tables.

  1. National base. The CPHEEO Manual on Storm Water Drainage Systems (2019). This Manual builds on it and sets higher standards where it allows a State to do so. IRC road-drainage codes and the NDMA urban flood guidelines are also used.
  2. Overall structure. Kansas City Metro APWA Section 5600 (Version 2025.01), the most recent comprehensive regional standard. It supplies the preserve, retain, detain, convey and maintain sequence and the required retention volume.
  3. Design rainfall. Frequency analysis of hourly rainfall by the National Institute of Hydrology (NIH), Roorkee.
  4. Tropical and coastal practice. The PUB Singapore Code of Practice on Surface Water Drainage (7th ed., 2025), for the fixed-coefficient route for small sites, drainage reserves and coastal platform levels. Malaysia's MSMA 2 (2012), for monsoon design storms and simplified on-site detention.
  5. Runoff reduction and treatment. The Georgia Stormwater Management Manual (2016), for runoff reduction and downstream analysis. CIRIA C753 The SuDS Manual (2015), for the treatment train. The Mile High Flood District criteria manual, for outlet and storage design.
  6. Local rules. The Andhra Pradesh Building Rules, 2017 (APBR), the Andhra Pradesh Land Development (Layout and Sub-division) Rules, 2017, the Andhra Pradesh Water, Land and Trees Act, 2002 (APWALTA), and the CRZ Notification 2019 as applied in Andhra Pradesh, which this Manual follows or, where disclosed, makes stricter.

Why this Manual is needed

India has no uniform stormwater design standard. The CPHEEO Manual on Storm Water Drainage Systems (2019) is the country's first manual dedicated to storm water drainage, but it is advisory. The Ministry of Housing and Urban Affairs lists it among advisory guidelines and treats urban flooding as a matter for State Governments and urban local bodies. None of the national rules or State building rules reviewed for this Manual makes runoff control a condition of building approval. APBR 2017, APWALTA 2002 and the Model Building Bye-Laws 2016 require rainwater harvesting, but they set no detention volume and no release rate. APBR sets no storage volume even for rainwater harvesting, beyond one recharge bore for every 5,000 m² of built-up area on large projects.

The national documents leave key values open, or give different answers.

  • Return periods. CPHEEO recommends 5 years for drains in Class I cities and 2 years elsewhere, and lets a State committee adopt higher values. A 2023 CPHEEO presentation shows a different table. IRC:SP:50-2013 suggests 1–2 years for urban road drains; IRC:SP:42-2014 suggests 25 years. An engineer designing a drain on a Visakhapatnam arterial road can cite 1, 5 or 25 years, depending on the code chosen.
  • Detention. CPHEEO describes limiting peak outflow to pre-development rates as general practice. It uses no "shall" and names no storm frequencies.
  • Climate. The NDMA Urban Flooding Guidelines (2010) call for detention and retention facilities and for rainfall curves adjusted for climate change, but give no sizing rule or return period.
  • Design rainfall. No national document gives design rainfall that a designer can apply directly to a given town. Each project chooses its own source. The Amaravati flood works were designed for a 1-in-100-year rainfall of 222 mm in a day, while the same study read 260–280 mm from IMD's isopluvial maps for the area.

Andhra Pradesh has no drainage design standard of its own. Research for this Manual found no Andhra Pradesh design standard, State IDF relationship or departmental circular that fixes return periods or design rainfall for urban drains, and no published IDF for any city in the State. No State rule requires on-site detention. The only published city drainage criteria found are those of the Amaravati capital city, where APCRDA designed the city drains for a 1-in-5-year storm and the Kondaveeti Vagu flood system for a 1-in-100-year flood; no stormwater drainage master plan was found for Visakhapatnam, Vijayawada, Guntur, Nellore, Tirupati or Kakinada. CAG found in its audit for the year ended March 2018 that none of the towns it test-checked had the storm water management plan that the Ministry of Urban Development had advised in 2013, and that the State authority under APWALTA had not been notified since the bifurcation of 2014. In its audit for the year ended March 2021 it found that Amaravati's "Blue Master Plan" for flood protection was still at a preliminary stage, with ₹3,213.41 crore spent on stalled trunk works, including reservoirs and stream development.

So each region and each local body interprets the central manual its own way. Corporations, municipalities, panchayats, development authorities, consultants and funding agencies fill the gaps differently. Two drains on the same street, built by different agencies, can be sized for different storms from different rainfall sources. Neighbouring local bodies in one river basin can work to different standards, though the water does not stop at their boundary. A city drain can be designed without regard to the Water Resources Department stream or delta drain it empties into, as the Budameru showed in 2024. And a reviewer has no common basis against which to check a design.

What this Manual does about it. It turns those open choices into one State standard:

  • one source and method for design rainfall (Chapter 2);
  • named return periods for every drainage element (Chapters 2 and 6);
  • a required pre- versus post-development rule for private sites (Chapter 4);
  • a required tailwater check for outfalls (Chapter 5); and
  • basin-wide master plans, so that neighbouring local bodies plan together (Chapter 11).

It uses the route the CPHEEO manual itself provides: a State may adopt standards higher than the national values (CPHEEO 2019, Table 4.1, Note 2). A Municipal Corporation, Municipality, Nagar Panchayat, Gram Panchayat or development authority can still adopt a stricter standard (Chapter 1).

Sources: CPHEEO (2019) Part A §4.4–4.5 and Table 4.1; CPHEEO presentation to CSE (August 2023); IRC:SP:50-2013 §6; IRC:SP:42-2014 §6; NDMA (2010) Urban Flooding Guidelines; MoHUA Model Building Bye-Laws (2016); Lok Sabha Unstarred Question 1847 (July 2026); APBR 2017 (G.O.Ms.No.119 MA&UD, 28-03-2017), Rules 152–155; APWALTA 2002 s.17; APCRDA, EIA-EMP for Flood Management Works, Amaravati (2018); CAG, Report on Economic Sector and PSUs, Government of Andhra Pradesh, year ended March 2018, para 3.1; CAG, Compliance Audit, Government of Andhra Pradesh, year ended March 2021, Chapter II, para 2.1; Ministry of Jal Shakti, First Census of Water Bodies (reference year 2017-18), Andhra Pradesh; Deccan Chronicle (31 August 2024; 26 July 2025); SANDRP (4 September 2024), from CWC data; IMD, report on VSCS Hudhud (2014).


How to use this Manual

Clauses and commentary. Numbered clauses (for example 4.5.2) are the requirements of this Manual and use "shall". Paragraphs headed Commentary explain the reason for a clause and cite its precedent. They are guidance, not requirements. Where a value has no direct precedent elsewhere, the commentary says so and explains why this Manual sets it.

Return periods. Storms are described both by annual exceedance probability (AEP) and by return period. For example, "1% AEP (100-yr)" means a storm with a 1-in-100 chance of being equalled or exceeded in any year.

Illustrative values. Worked examples and figures marked "Illustrative — not design values" show method and scale only. Design values come from the sources set in Chapter 2.

Annexes and forms. Each chapter lists the annexes and forms it relies on. They follow the chapters, grouped by chapter, and hold the forms to submit, worked examples, templates, model text and standard drawings. Annexes that need data not yet collected are marked To be prepared. They say what they will contain, and the clause that depends on them states the rule that applies in the meantime.

Supplements. The supplement follows the annexes. It applies the Manual to a Union Territory area that lies within Andhra Pradesh, and states where its rules differ.

Figures. All figures are original drawings prepared for this Manual. Where a figure follows a published concept, its caption credits the source.

Where to start.

If you are… Read first
A developer or architect Chapter 1 (does it apply?), Chapter 4 (what to provide), Chapter 10 (what to submit)
A design engineer Chapters 2–6, then 8 and 9
A local body or approving authority Chapters 1, 10 and 11
A planner or waterbody manager Chapters 7 and 11

Contents

Ch Title Annexes and forms
1 Policy, Applicability and Adoption Annexes 1
2 Design Rainfall and Design Storms Annexes 2
3 Hydrologic Methods Annexes 3
4 Site Runoff Control: Retention and Detention Annexes 4
5 Downstream and Tailwater Analysis Annexes 5
6 Minor and Major Drainage Systems Annexes 6
7 Waterbodies, Tanks (Cheruvulu) and Setbacks Annexes 7
8 Water Quality and Recharge Annexes 8
9 Hydraulic Design of Structures Annexes 9
10 Submittals, Review, Operation & Maintenance and Enforcement Annexes 10
11 Basin and City Stormwater Master Plans Annexes 11

Supplements

No. Title Status
S01 Yanam (Union Territory of Puducherry) Not adopted by the Government of Puducherry

List of tables

TableTitle
1.1Differences between Tier A and Tier B authorities
1.2Policy supplement: adoptable alternatives S-1 to S-5
1.3Relationship with other instruments
1.4Roles and responsibilities under this Manual
2.1Design return periods (summary)
2.2Interim climate factors
2.3Illustrative scale of the mixed-frequency rule (not design values)
3.1Permitted hydrologic methods
3.2Runoff coefficient C (for AEP of 10% or more frequent)
3.3Frequency factor Cf
3.4Manning's n for sheet flow (USDA SCS TR-55, 1986, Table 3-1)
3.5Runoff curve numbers, AMC II, Ia = 0.2S (USDA SCS TR-55, 1986, Tables 2-2a and 2-2c)
4.1Design storms to be routed for detention sizing
4.2Illustrative example: peak discharges and storage used, by duration (Illustrative — not design values)
4.3Tier B permissible site discharge and site storage requirement (template)
4.3AFixed release coefficients (provisional)
5.1Design tailwater levels for tidal outfalls
5.2Joint-probability cases for tidal and riverine outfalls
6.1Design AEPs for conveyance (matches Clause 2.4)
6.2Street flow limits
6.3Flow hazard limits for streets and overland flow paths
6.4Combined flood hazard vulnerability classes (reproduced for reference)
6.5Inlet clogging factors (share of clean capacity assumed lost)
6.6Manning's n for design (from CPHEEO 2019)
6.7Minimum freeboard in open and covered drains
6.8Maximum spacing of manholes on straight pipe runs
6.9Minimum drainage reserve width (adopted from PUB Singapore)
7.1Fixed-width setback where no 1% AEP extent is available
8.1Pollutants of concern, sources and primary controls
8.2Required Level of Service for sites that are not redevelopment
8.3BMP Value Ratings and suitability in Andhra Pradesh
9.1Entrance loss coefficients ke (outlet control, full or partly full)
9.2Maximum permissible mean velocities in channels
9.3Riprap classes and apron dimensions (HEC-14)
9.4Minimum internal size of manholes
9.5Minimum IS 456 exposure classes for Andhra Pradesh locations
10.1Submittal stages and linked approvals
10.2Forms used in submittals
10.3Minimum owner inspection frequencies
10.4Graduated enforcement response
11.1Minimum data and surveys for a BSMP
11.2Minimum levels of service
1A.1Tier A authorities as defined in Clause 1.6.1
1A.2Register of Tier A authorities (layout)
1B.1Flood-sensitive catchments listed in Clause 4.5.3.2
1B.2Attributes of the flood-sensitive catchment layer (layout)
1C.1Alternatives adopted by this resolution
1D.1Schedule: alternatives adopted (layout)
2A.1Benchmark comparison of design depths (layout)
2A.2Rainfall zones (layout)
2B.1Ratios P(t)/P(24h) by zone (layout)
2B.2Fixed-interval adjustment factors (Clause 2.6.3)
2C.1Grid-to-point factors (layout)
2D.1Cumulative fraction of storm depth against cumulative fraction of storm time (layout, one table per zone, duration class and quartile)
2E.1Retention depth P_R by zone (layout)
3A.1Soil series to HSG lookup (layout)
3A.2Seasonal high water table, by mapping unit (layout)
3B.1Supplementary land covers, AMC II (layout)
3B.2CN calibration catchments (layout)
3C.1Problem 3C-1 solution
3C.2Problem 3C-2 solution
3C.3Problem 3C-3 solution
3C.4Problem 3C-4 solution
3C.5Problem 3C-5 stage–storage–discharge relationship
3C.6Problem 3C-5 routed outflow
3C.7Benchmark results to be reported by the applicant
3D.1Calibrated peak rate factors (layout)
3E.1SUH relationships by subzone (layout)
3E.2Worked example outline (layout)
4A.1Attributes of the shallow-groundwater zone layer (layout)
4B.1Contents of Annex 4B and their status
4B.2Tier B PSD and SSR (layout of Table 4.3)
4B.3Retention credit factor C_R (layout)
4B.4Largest orifice diameter (mm) for a permissible discharge at a given head (Cd = 0.60, free discharge)
4B.5Fixed release coefficients C_10 and C_2 (provisional, Table 4.3A)
4C.1Inputs (Illustrative — not design values)
4C.2Design rainfall depths, mm (Illustrative — not design values)
4C.3Curve numbers and abstractions (Illustrative — not design values)
4C.4Storm runoff depth Q, mm (Illustrative — not design values)
4C.5Unit hydrograph parameters (Illustrative — not design values)
4C.6Stage–storage–discharge, trial outlet (Illustrative — not design values)
4C.7Routing of the 100-yr 72-hour storm through the trial outlet, around the peak (Illustrative — not design values)
4C.8Routing of the 100-yr 72-hour storm through the trial outlet, hourly (Illustrative — not design values)
4C.9Results for the trial outlet (120 mm and 470 mm orifices) (Illustrative — not design values)
4C.10Stage–storage–discharge, revised outlet (Illustrative — not design values)
4C.11Results for the revised outlet (170 mm and 460 mm orifices) (Illustrative — not design values)
4C.12Retention credit by routing, revised outlet (Illustrative — not design values)
4C.13Outlet checks, revised outlet (Illustrative — not design values)
4C.14Summary of the revised design (Illustrative — not design values)
5A.1Use of the Annex 5A values in the design tailwater (Table 5.1)
5A.2Tidal datums, surge and still-water levels by coastal segment (layout)
5B.1Water bodies named in Chapter 5
5B.2Attributes of the Annex 5B layers (layout)
5C.1Inputs (Illustrative — not design values)
5C.2Outfall-closed check results (Illustrative — not design values)
5C.3Volume balance, 1% AEP 48-hour storm, Run B (Illustrative — not design values)
5C.4Stage hydrograph, 1% AEP 48-hour storm, Run B (Illustrative — not design values)
5C.5Summary (Illustrative — not design values)
6A.1Interim requirements for inlets until Annex 6A is published (from Chapters 6 and 9)
6A.2Register of standard inlet types (layout)
6A.3Capacity on grade (layout; one table per inlet type)
6A.4Capacity in a sag (layout; one table per inlet type)
6B.1Sediment allowances already set by Chapter 6 (provisional, to be calibrated)
6B.2Sediment yield by land use and drain type (layout)
6B.3Calibration of the sediment allowance (layout)
6C.1Dimensions on the standard drawings and their source clauses
7A.1Attribute fields of the waterbody inventory (WB_POLY)
7A.2Code lists
7A.3Attribute fields of structures (WB_STRUCT)
7B.1Fixed-width setback by waterbody class (alternative S-3)
7B.2Source buffers cited in Clause 7.4.6 (KC APWA 5600, 2006, §5605.3)
7C.1Rule levels by period (to be completed for each tank)
7C.2Outlet settings by level (to be completed for each tank)
7C.3Triggers and actions (to be completed for each tank)
7D.1Hold points for desilting and restoration works
7E.1Waterbodies
7E.2Parts of a tank and its system
7E.3Flood terms
8A.1Water quality rainfall depths by zone (layout)
8A.23-month ARI intensity by duration (layout)
8B.1Required LoS for redevelopment (layout)
8B.2Worked example: composite VR (illustrative)
8B.3Composite VR of treatment trains (layout)
8C.1Monitoring site register (layout)
8C.2Event record (layout; parameters of Clause 8.13.2)
8C.3Performance summary and proposed VR (layout)
8D.1Pretreatment (all BMPs)
8D.2Bioretention and rain gardens (Figure 8.2)
8D.3Vegetated swales
8D.4Vegetated filter strips
8D.5Permeable pavement
8D.6Infiltration trenches and basins (Figure 8.3)
8D.7Wet ponds (extended wet detention)
8D.8Constructed wetlands
8D.9Gross pollutant traps and outfall screens
8D.10Oil-grit separators
8D.11Infiltration and recharge criteria (all infiltrating BMPs)
8D.12Bioretention filter media and layers
8D.13Indicative plants for bioretention, swales and filter strips
8D.14Indicative plants for constructed wetlands and wet ponds
8D.15Species not to be planted
8E.1Selection of measures (Clause 8.12.3)
8E.2ESC timing and inspection (Clauses 8.12.2 and 8.12.5)
9A.1HDS-5 inlet-control coefficients for common inlets
9A.2Inputs for the worked example
9A.3Critical depth and specific head (D = 1.2 m)
9A.4Inlet-control headwater
9A.5Outlet-control headwater
9A.6Governing headwater and checks
9A.7Riprap apron sizing
9A.8Summary of the worked example (Illustrative — not design values)
9B.1Dimensions and rules on the standard drawings and their source clauses
9C.1Pump station design checklist
9C.2Control levels (values to be set in design)
10A.1Calculator inputs
10A.2Calculations the calculator shall perform
10B.1Layers
10B.2Attributes of SW_FAC (facilities)
10B.3Attributes of SW_OUTF (outfalls)
10B.4Attributes of SW_CATCH (catchments)
10B.5Attributes of SW_FLOW and SW_CONV (flow paths and conveyance)
10B.6Metadata (SW_META)
10B.7Facility type codes (FAC_TYPE)
10B.8Status codes (STATUS)
10B.9Inspection result codes (INSP_RES)
10C.1Access dimensions set by the Manual
10C.2Access dimensions not set by the Manual (to be confirmed in design)
10D.1Contents of an O&M plan
10D.2Retention and infiltration (soakaways, trenches, bioretention, permeable paving)
10D.3Surface detention basin or multi-use open space area
10D.4Underground or podium detention tank, gravity outlet
10D.5Pumped detention, pumps and controls
10D.6Flap or tide gate, non-return valve
10D.7Gross pollutant trap or first-flush device
10D.8Private drains and inlets
11A.1Deliverables
11B.1Basins named in Clause 11.3.3 (provisional)
11B.2Attributes of the basin boundary layer (layout)
11C.1Depth–damage curve (layout, one table per building type)
11D.1Items to be published
S1.1Modifications to the Manual for the Yanam region
S1.2Roles in the Yanam region
S1.3Godavari flood at Yanam, July 2022

List of figures

FigureTitle
1.1Stormwater management hierarchy
1.2Applicability decision flowchart
2.1Design rainfall source hierarchy and adjustments
2.2Design hyetographs
2.3From design rainfall source to design storm
3.1Selection of hydrologic method
3.2Time of concentration: flow segments along the longest flow path (schematic)
3.3SCS-CN runoff depth versus rainfall depth
3.4Two-step continuous simulation: starting tank level (schematic)
3.5Pre- and post-development hydrographs
4.1Pre-development 10-yr, post-development 100-yr uncontrolled, and detained hydrographs (illustrative)
4.2Detention storage stack and multi-stage outlet (schematic)
4.3Fixed-coefficient route: release caps, storage by the mass-curve method and two-stage outlet (schematic)
5.1Extent of downstream analysis
5.2Tidal outfall section with flap gate and design tailwater levels
5.3Tide-locked outfall timeline (illustrative)
6.1Minor and major drainage in a kerbed street
6.2Gutter spread, inlet interception and clogging
6.3Drain sections: freeboard, sediment allowance and access
6.4Drainage reserve: cross-section (schematic)
6.5Coastal band: floor level stack and extent of the band (schematic)
7.1Waterbody setback zones
7.2Compensatory storage by elevation band (schematic)
7.3Tank (cheruvu) cascade
8.1Treatment train
8.2Bioretention cell
8.3Infiltration trench
9.1Culvert hydraulics: inlet control and outlet control
9.2Riprap apron at a pipe or culvert outlet (schematic)
9.3Stormwater pump station: wet well, screens, levels and outfall
10.1Submittal, review and approval workflow
10.2Construction hold points from approval to handover
10.3Maintenance cycle and responsibility
11.1Basin master plan process
11.2BSMP model schematic
6C.1Covered roadside drain with removable covers
6C.2Access and junction chamber on a covered drain
6C.3Kerb inlet with silt sump
8E.1Silt fence: section and plan (schematic)
8E.2Sediment basin with surface dewatering outlet: section (schematic)
8E.3Stabilised construction exit: plan and section (schematic)
8E.4Drain inlet protection (schematic)
9B.1Culvert headwalls, wingwalls and cut-off walls
9B.2Straight vertical drop structure
9B.3Trash rack at a conduit entrance
9B.4Detention outlet riser and emergency spillway

Abbreviations

Abbreviation Meaning
AEP Annual exceedance probability
AMC Antecedent moisture condition
AMRUT Atal Mission for Rejuvenation and Urban Transformation
APBR Andhra Pradesh Building Rules, 2017
APCRDA Andhra Pradesh Capital Region Development Authority
APCZMA Andhra Pradesh Coastal Zone Management Authority
APDPMS Andhra Pradesh Development Permission Management System (online building and layout approvals)
APPCB Andhra Pradesh Pollution Control Board
APSAC Andhra Pradesh Space Applications Centre
APSDMA Andhra Pradesh State Disaster Management Authority
APWA American Public Works Association
APWALTA Andhra Pradesh Water, Land and Trees Act, 2002
ARF Areal reduction factor
BSMP Basin Stormwater Master Plan
CAG Comptroller and Auditor General of India
CDMA Commissioner and Director of Municipal Administration, Andhra Pradesh
CN Curve number (SCS/NRCS method)
CPHEEO Central Public Health and Environmental Engineering Organisation
CRZ / CZMP Coastal Regulation Zone / Coastal Zone Management Plan
CSE Centre for Science and Environment
CWC Central Water Commission
DDMA District Disaster Management Authority
DTCP Directorate of Town and Country Planning, Andhra Pradesh
FTL / MWL Full tank level / maximum water level
GVMC Greater Visakhapatnam Municipal Corporation
HAT / MHWS Highest astronomical tide / mean high water springs
HGL Hydraulic grade line
HSG Hydrologic soil group
IDF Intensity–duration–frequency
IMD India Meteorological Department
IRC Indian Roads Congress
MA&UD Municipal Administration and Urban Development Department, Andhra Pradesh
MoHUA Ministry of Housing and Urban Affairs
NDMA National Disaster Management Authority
NE monsoon / OND North-east monsoon, October–December
NIH National Institute of Hydrology, Roorkee
PHMED Public Health and Municipal Engineering Department, Andhra Pradesh
PR&RD Panchayat Raj and Rural Development Department, Andhra Pradesh
PSD Permissible site discharge
RRV Required retention volume
RTGS Real Time Governance Society, Andhra Pradesh
RWH Rainwater harvesting
SLA Sea-level allowance
SW monsoon / JJAS South-west monsoon, June–September
UDA Urban Development Authority
ULB Urban local body (Municipal Corporation, Municipality or Nagar Panchayat)
VMC Vijayawada Municipal Corporation
VMRDA Visakhapatnam Metropolitan Region Development Authority
WQv Water quality volume
WRD Water Resources Department, Andhra Pradesh