Chapter 2Design Rainfall and Design Storms
2.1 Purpose and scope
2.1.1 This chapter sets the rainfall inputs for every hydrologic calculation in this Manual: drain and inlet sizing (Chapter 6), retention and detention sizing (Chapter 4), downstream and tailwater analysis (Chapter 5), and waterbody and tank works (Chapter 7).
2.1.2 It specifies:
- (a) the approved sources of design rainfall depth and intensity;
- (b) how depths are converted between durations, between point and area, and from present to future climate;
- (c) how design storms (hyetographs) are constructed; and
- (d) the storms that must be applied to pre- and post-development conditions.
2.1.3 This chapter applies throughout Bihar. Where a Nagar Nigam, Nagar Parishad, Nagar Panchayat or PMAA has adopted a stricter rainfall standard under Chapter 1, the stricter standard governs.
2.2 Definitions
| Term | Meaning in this Manual |
|---|---|
| Annual exceedance probability (AEP) | Probability that a given rainfall depth is equalled or exceeded in any one year. A 1% AEP storm is the "100-year" storm. Both forms are used here: T-year = 1/AEP. |
| IDF / DDF | Intensity–duration–frequency and depth–duration–frequency relationships for a location. |
| Point rainfall | Rainfall at a single location, as measured by a rain gauge. |
| Design storm | A hyetograph (rainfall depth versus time) of stated AEP, duration and temporal pattern. |
| Critical duration | The storm duration that produces the largest peak flow, water level or storage requirement for the element being designed. |
| Areal reduction factor (ARF) | Ratio of catchment-average rainfall to point rainfall for the same AEP and duration. |
| SW monsoon season (JJAS) | June–September, when Bihar receives about 86% of its annual rainfall, with July (about 28%) and August (about 24%) the wettest months. The State's annual normal is 1,191.2 mm (1951–2000), from 857.9 mm at Arwal and 858.2 mm at Jahanabad in the south-west to 2,215.0 mm at Kishanganj in the north-east; Patna 984.7 mm, Gaya 941.3 mm, Muzaffarpur 1,151.0 mm and Purnea 1,732.8 mm (IMD). The normal date of onset is 13 June at Purnea, 16 June at Patna and Gaya and 18 June at Chhapra, and of withdrawal 6 October at Chhapra, 8 October at Patna, 9 October at Gaya and 10 October at Purnea (IMD, new normals of 2020); in 2025 the monsoon withdrew from the whole State on 13 October (as reported). The north-east is wet before the season begins, with May normals of 166.5 mm at Kishanganj, 127.4 mm at Purnea, 120.2 mm at Araria and 105.9 mm at Katihar, and June normals of 266.8–374.7 mm there, against 27.6 mm in May and 116.4 mm in June at Patna (IMD). The antecedent moisture rule of Clause 2.11.4 refers to this season; the pre-monsoon deadline of 31 May is set ahead of the earliest onset, with an earlier date in the north-east (Chapter 10). |
| Storms outside the season | Large falls come before and after it: 271.8 mm at Motihari on 29 May 2006, 220.5 mm at Purnea on 27 May 1887, and 214.6 mm at Sabour and 172.0 mm at Bhagalpur on 22 April 1971 before the monsoon; 458.2 mm at Buchaha (Muzaffarpur) and 374.0 mm at Sheikhpura on 3–4 October 1961, 243.0 mm at Chapra on 5 October 1977, 196.0 mm at Bhagalpur on 20 October 1987 and 162.6 mm at Patna (A) on 6 October 1946 at or after its normal withdrawal; and 745.1 mm at Motihari in May 1993 (IMD). Of the 113 storms and depressions that affected Bihar in 1891–2010, 43 came in September, 18 in August, 17 each in June and October, 12 in July, 5 in May and 1 in November (IMD). Design statistics use annual maxima from all months, and no works deadline or operating rule shall assume that heavy rain is confined to June–September. |
| Climate factor (CF) | Multiplier applied to present-day design depths to represent the design-life climate. |
| Approved source | A rainfall source listed in Clause 2.3. |
2.3 Approved sources of design rainfall
2.3.1 Primary source. Design rainfall depths and intensities shall be taken from the National Institute of Hydrology, Roorkee NIH-DHAARA platform (Design Hydrology and Advanced Rainfall Analysis, nihdhaara.in). Use its IDF / frequency tools for the site's coordinates, for each duration and AEP required by Clause 2.4. In Bihar this clause is suspended until Annex 2A is published: Clause 2.3.6 sets the interim source.
2.3.2 Station IDF. A station-specific IDF relationship may be used in place of 2.3.1 only if all of the following hold:
- (a) it is derived from at least 30 years of recording-gauge (hourly or finer) data;
- (b) it has been published or approved by IMD, the State Hydrology Authority or the approving authority; and
- (c) the gauge is within 10 km of the site, with no major change of terrain or coastal exposure in between.
Where a station IDF is used, the design value shall be the greater of the station value and the NIH-DHAARA value.
2.3.3 Cross-checks (mandatory, not alternatives). The designer shall report, but need not adopt, the following values for comparison:
- (a) the IMD isopluvial / IDF values of Das et al. (2022), MAUSAM 73(4), for durations of 1–24 h;
- (b) for catchments of 25–5,000 km², the 24-hour point rainfall from the CWC Flood Estimation Report for subzone 1(d) (Sone), 1(f) (Middle Ganga Plains) or 1(g) (Lower Ganga Plains), as applicable.
Where the design value is lower than the CWC 1(d)/1(f)/1(g) value for the same AEP, the CWC value shall be adopted as a floor.
2.3.4 Not permitted. None of the following shall be used as a design rainfall source:
- (a) generalised all-India IDF formulae (for example Kothyari & Garde, 1992);
- (b) rainfall values that cite no source, including vendor or web-calculator tables;
- (c) single-event maxima; or
- (d) design intensities carried forward from a previous project without a stated AEP.
Figure 2.1 — Design rainfall source hierarchy and adjustment sequence. Original drawing for this Manual.
2.3.5 Version control. Every submittal shall record the source, its version or access date, the coordinates queried, and the values extracted (Clause 2.13).
2.3.6 Interim source in Bihar. Until Annex 2A is published and confirms NIH-DHAARA, or an approved station IDF, for a zone, Clause 2.3.1 does not apply in Bihar, and design rainfall shall be taken as follows:
-
(a) Station IDF. Where a station IDF fitted to a checked IMD recording-gauge (SRRG) or automatic weather station record of at least 25 years has been published in Annex 2B, it governs, within 10 km of the station, for the durations and AEPs it covers, in place of (g) and (h); the comparison of Clause 2.3.2 is then made with the 24-hour and longer depths of (d) to (f), and the CWC floor of Clause 2.3.3 still applies. A record is checked when its annual totals and annual maxima have been compared with the IMD normals and station extremes for the station, and every year that disagrees has been explained or removed. An IDF derived from daily data by the one-third rule (Clause 2.6.4) or by any other fixed ratio is not a station IDF. In Bihar Clause 2.3.2(a) is read with 25 years in place of 30 (set by this Manual, so that the recording gauges of the State's main cities can qualify once analysed). No IDF has yet been published in Annex 2B, and none was found for any city in the State.
-
(b) Patna and the Punpun basin. The only sub-daily frequency analysis for any part of Bihar located in research for this Manual is a research report of the National Institute of Hydrology on the characteristics of short-interval rainfall in the Punpun basin, which drains south Patna; it is reported to give depth–duration–frequency curves for 5 to 100 years from hourly gauges, fitted by L-moments to the GEV distribution, but it was seen only through a summary and was not obtained [TBC]. It is not used until it has been obtained, its records have been checked as in (a) and its values have been published in Annex 2B. Patna has no published station IDF; the 1-, 3- and 6-hour depths at every site in the State are those of (g) and (h).
-
(c) Subzone. The site's CWC subzone is that of the Flood Estimation Report whose area contains it, by the boundaries drawn on the reports' plates. The Ganga divides the State: 1(f) (Middle Ganga Plains, GP/10/1984, 1985) covers all of the State north of the Ganga, including West and East Champaran, Gopalganj, Siwan, Saran (Chhapra and Sonpur), Vaishali (Hajipur), Muzaffarpur, Sitamarhi, Sheohar, Darbhanga, Madhubani, Samastipur, Begusarai, Khagaria, Saharsa, Supaul, Madhepura, Purnia, Araria, Kishanganj, Katihar and Bhagalpur district north of the river (Naugachia); 1(d) (Sone, S/15/1987, 1987) covers the State south of the Ganga and west of the Kiul (about 86.2° E), including Patna city with Danapur, Phulwari and Khagaul, Bhojpur (Arrah), Buxar, Rohtas (Sasaram and Dehri), Kaimur (Bhabua), Jehanabad, Arwal, Gaya, Aurangabad, Nawada, Nalanda (Bihar Sharif and Rajgir), Sheikhpura and Lakhisarai west of the Kiul; and 1(g) (Lower Ganga Plains, LG-1(g)/R-1/23/94, 1994) covers the south-east, Munger with Jamalpur, Bhagalpur south of the Ganga (Bhagalpur city, Sultanganj and Kahalgaon), Banka, Jamui and Lakhisarai east of the Kiul. Within 5 km of a subzone boundary, the higher of the two plate values is used, and at each duration the higher of the two products under (g). Because the Ganga is itself the boundary between 1(d) or 1(g) and 1(f), this applies to the riverside parts of Patna, Hajipur, Sonpur, Mokama, Begusarai, Munger and Bhagalpur. The district lists are a guide: the plate boundaries govern, and are to be confirmed on the reports' index maps [TBC]. The rainfall zone and sub-area of the site are those of Annex 2A.
-
(d) 24-hour depth, 2% and 1% AEP (50- and 100-yr). The 24-hour point value at the site read from the 50- and 100-year isopluvial plates of the report for its subzone (Plates 9 and 10 of 1(d), by their titles, although the text of that report calls Plate 10 the 50-year map; Plates 8 and 9 of 1(f); and Plate 9 of 1(g) with that report's 100-year plate, whose number is to be confirmed [TBC]), whatever the catchment area. Where the site lies between two contours, the higher contour value is used; where it lies inside a closed contour with no higher contour within it, the value is that contour plus one contour interval (set by this Manual). Plates are read by the coordinates of the site, not by the town labels, one of which (Kishanganj, on the 1(f) plate) is misplaced. For orientation only, read by eye to about one contour, the 50-year plates give about 260–280 mm at Patna, 240–280 mm at Arrah and Sasaram, about 280 mm at Bihar Sharif and Rajgir, 280–320 mm at Gaya, less than 240 mm at Lakhisarai, 240–280 mm at Hajipur, Chhapra and Katihar, 280–320 mm at Darbhanga, Begusarai, Motihari and Purnia, about 320 mm at Muzaffarpur and Saharsa, 320–360 mm at Kishanganj, more than 400 mm in a cell at Bagaha and Valmikinagar on the Nepal border, 280–320 mm at Munger and Bhagalpur and about 240 mm at Banka; the 100-year values are about one contour (40 mm) higher. The worked example of the 1(f) report, on the Muzaffarpur–Sagauli railway line, reads 340 mm at 50 years. Where the Gumbel estimate of (e) for the station of the site is higher for the same AEP, it governs.
-
(e) 24-hour depth, 50%, 20%, 10% and 4% AEP (2-, 5-, 10- and 25-yr). The reports have no plates for these. The depth is the Gumbel (EV1) estimate from the annual maximum daily rainfall series, of all months, of the IMD station agreed with the Authority, checked as in (a), multiplied by the fixed-interval factor of Clause 2.6.3. The station is, for example, Patna (A), 42492 (daily record from 1946), for Patna; Gaya (A), 42591 (from 1896); the higher of Bhagalpur, 42498 (from 1950), and Sabour, 42499 (from 1931), for Bhagalpur; Muzaffarpur, 42387 (from 1901); Darbhanga, 42391 (from 1901); Purnea, 42500 (from 1874), for Purnia; Chapra, 42488; Motihari, 42383; Forbesganj, 42395; Supaul, 42393; or Dehri, 42588. Arrah, Bihar Sharif, Begusarai, Katihar and Kishanganj have no long-record IMD station; for them, and elsewhere, the station is the nearest IMD station with 30 or more years of record, from the candidates in Annex 2A.
-
(f) 48- and 72-hour depths. The Gumbel estimate from the annual maximum 2-day and 3-day rainfall series of the same station, with the fixed-interval factors of Clause 2.6.3, and not less than the 24-hour depth for the same AEP.
-
(g) Durations of 1 to 24 hours. The 24-hour depth of (d) or (e) multiplied by the ratios of the report for the site's subzone in Table 2B.1, at every AEP: in 1(d), the 50-year ratios 0.37 at 1 hour, 0.58 at 3 hours, 0.70 at 6 hours, 0.80 at 9 hours, 0.89 at 12 hours, 0.94 at 15 hours and 0.98 at 18 hours, which the report found independent of the return period from 5 years upward (the 18-hour value from an OCR of the report, not checked against the page image [TBC]); in 1(f), the 50-year ratios 0.31 at 1 hour, 0.425 at 2 hours, 0.50 at 3 hours, 0.555 at 4 hours, 0.605 at 5 hours, 0.65 at 6 hours, 0.75 at 9 hours, 0.82 at 12 hours, 0.89 at 15 hours and 0.94 at 18 hours; and in 1(g), the ratios 0.350 at 1 hour, 0.515 at 3 hours, 0.640 at 6 hours, 0.735 at 9 hours, 0.800 at 12 hours, 0.860 at 15 hours and 0.915 at 18 hours. Between the tabulated durations the ratio is interpolated on logarithmic axes. The 1-, 2- and 3-hour depths are then subject to (h).
-
(h) Floor for short storms, 10-yr and rarer. The 1-hour and 3-hour depths shall be not less than the greater of (i) 0.35 times (1 hour) and 0.57 times (3 hours) the 24-hour depth of (d) or (e) for the same AEP, and (ii) the following values for the site's zone of Annex 2A, all set by this Manual; the 2-hour depth shall be not less than the value interpolated on logarithmic axes between the 1- and 3-hour values for the same AEP:
Zone Duration 10% (10) 4% (25) 2% (50) 1% (100) BR-Z1 South Bihar; BR-Z2 North Bihar plain 1-hour depth not less than (mm) 80 95 105 115 BR-Z1 South Bihar; BR-Z2 North Bihar plain 3-hour depth not less than (mm) 130 155 175 195 BR-Z3 Seemanchal and Champaran terai 1-hour depth not less than (mm) 90 110 120 135 BR-Z3 Seemanchal and Champaran terai 3-hour depth not less than (mm) 150 180 200 220 The reason is that no station in Bihar has a published short-duration frequency analysis against which the subzone ratios, derived in 1984–1994 from recording-gauge data averaged over each subzone, can be tested, and that in the one place in the same Gangetic plain where such a test has been made, they fall short. At Lucknow, in subzone 1(f) in Uttar Pradesh, a station fit to about 25 years of hourly records gives 106.0 mm in 1 hour and 174.6 mm in 3 hours for the 50-year storm, 22–43% more at 1 hour than the 1(f) plates and ratios give there, and the same paper's 2-year ratios of the 1-hour to the 24-hour depth at three stations of that plain are 0.35–0.38, and of the 3-hour depth 0.57–0.61, all above the 1(f) ratios of 0.31 and 0.50 and the 1(g) ratios of 0.350 and 0.515 (Kathuria, Kaur & Mehra, 1987); the ratio floor of (i) takes the lowest of the three stations at each duration. In 1(d) the subzone's own ratios, 0.37 and 0.58, already exceed it. The depths of (ii) for BR-Z1 and BR-Z2 are the values of that station fit at 10, 25, 50 and 100 years, rounded to 5 mm. They are applied in both zones because the 24-hour plate values there, about 240–320 mm, with Patna at about 260–280 mm, Gaya at 280–320 mm and Muzaffarpur at about 320 mm, are mostly equal to or higher than the 240–280 mm of the plate at Lucknow, and because nothing in the Bihar record suggests that short storms are smaller here. In BR-Z3, the wettest part of the State, where the 50-year plate values rise to 320–360 mm at Kishanganj and more than 400 mm near Valmikinagar, the annual normals are 1,390–2,215 mm and days of 445–510 mm have been recorded at Barsoe, Champatia, Bahadurganj and Dengraghat (IMD), the same values are scaled by 320/280 and rounded to 5 mm; where the 24-hour depth is larger still, the ratio floor of (i) governs. At Patna the 1(d) plates and ratios give about 96–104 mm in 1 hour and 151–162 mm in 3 hours for the 50-year storm, and the floors raise these to 105 mm and 175 mm. The few sub-daily maxima found for Bihar are single events at recording gauges with short records, 52 mm in 1 hour at Sabour on 19 May 1971 and 35 mm at Jamui in 1972 (CWC FER 1(g)), and they neither confirm nor rule out the floors; hourly falls of 98–100 mm have been recorded in the lower Gangetic plain of West Bengal (IMD), and the 24-hour records of the State's stations reach 1.5–2 times the 50-year plate values (Clause 2.3.6(d); Annex 2A). The floors are present-day, true-interval values: the fixed-interval factor of Clause 2.6.3 is not applied to them, and the climate factor of Clause 2.8 is. The floors are interim: they rest on a station fit outside the State, about 25 years of data that end before 1985, with standard errors of 10–12% at 50 years; no IMD hourly maximum for a recent storm in Bihar was found in research for this Manual [TBC]; and Annex 2B is to replace them with frequency analyses of the IMD recording-gauge and automatic weather station records of the State, beginning with Patna (A) and Patna (Anisabad), Gaya, Bhagalpur and Sabour, Muzaffarpur, Darbhanga and Purnea, and with the report of (b) once it is obtained.
-
(i) Durations below 1 hour. No sub-hourly frequency analysis for any station in the State was found in research for this Manual. Until Annex 2B gives one, the ratio of the depth for a duration below 1 hour to the 1-hour design depth is agreed with the Authority, from a published recording-gauge analysis whose source is stated, and recorded on Form 2-1 [TBC]; the average intensity for a duration below 1 hour shall be not less than the 1-hour design intensity for the same AEP (set by this Manual).
-
(j) Order of depths. For the same AEP, no depth shall be less than the depth for a shorter duration.
-
(k) NIH-DHAARA. Its present-day values at the site are reported on Form 2-1 beside the interim values, for comparison only: in the State they are too high at 24 hours over most of north Bihar, low at Gaya, and low at 1 hour everywhere (commentary). Its projected depths are not used under Clause 2.8.4; the ratio of its projected to its present-day depths may be reported as a check on the climate factors of Table 2.2, which apply.
-
(l) IMD Das et al. (2022). The paper has no panel for any station in Bihar, and its range for the Gangetic plain gives a 3-hour upper bound (14 cm) below its 1-hour upper bound (16 cm), which cannot hold at one place. The cross-check of Clause 2.3.3(a) is recorded on Form 2-1 as not available, and the paper is not used as a value, a check or a floor.
-
(m) Other clauses. Where Clauses 2.3.2, 2.6.1, 2.7.1 and 2.13, Annexes 2A to 2C and Form 2-1 refer to the NIH-DHAARA value, the value under this clause is meant.
Commentary. NIH-DHAARA is a national, publicly accessible product from a Government of India institution, and it can be queried at any point in the State. That makes it a reproducible default that an approving authority can check. NIH-DHAARA's sub-daily values are derived from hourly records, not disaggregated from daily totals. That makes it the only public source suitable for sizing drains, which depend on short-duration intensity. Its values should still be checked against the long IMD daily record at 24 hours and longer (Annex 2A). In Bihar the platform does not yet meet that purpose. Its present-day values there come from IMDAA reanalysis (about 12 km), not from gauges, and they err in both directions. Its 50-year 24-hour depths are far above the CWC plates over most of north Bihar: 526 mm at Kishanganj, against a plate value of about 320–360 mm; 404 mm at Purnia, against about 280–320 mm and a station record of 318.5 mm; 362 mm at Darbhanga, where the highest day in more than a century of record is 266.7 mm; and 351 mm at Katihar, against about 240–280 mm. At Gaya it is below both, 227 mm against a plate value of about 280–320 mm and a record of 290.8 mm. Near Patna (288 mm) it is close to the plate. Its 50-year 1-hour depths, 73–115 mm, are only 0.20–0.34 of its 24-hour depths, all below the CWC ratio of their own subzone (0.31–0.37); at Patna it gives 77.0 mm, 20–26% below the 96–104 mm of the 1(d) plates and ratios (NIH-DHAARA, queried 6 Nov 2026; IMD; CWC). A source that errs by these margins cannot be adopted, so Clause 2.3.6 uses the CWC reports and the long IMD station records until Annex 2A has been done, and uses NIH-DHAARA for comparison and as a check on the climate factors only. Bihar differs from its neighbours in one respect: three CWC subzones meet in the State, split by the Ganga, and the 1-hour ratio of the Sone subzone 1(d) south of the river, 0.37, is higher than that of any other Ganga-plain subzone (1(e) 0.34, 1(g) 0.350), while that of 1(f) north of it is 0.31, so the 1-hour screening depth changes by about a fifth across the river at Patna. That is why Clause 2.3.6(c) assigns Patna city to 1(d) and applies the higher value along the river, and why Clause 2.3.6(h) sets floors at 1 and 3 hours in every zone. The interim rules for the more frequent AEPs, the 48- and 72-hour depths, the reading of the plates, the subzone of each district, durations below 1 hour and the floors of (h) are set by this Manual. Several points are unresolved. The plate values were read by eye on scans, to about one contour, and the 1(f) plate near Darbhanga and Purnia needs a better copy [TBC]. The 1(f) ratios at 2, 4 and 5 hours and the 1(d) ratio at 18 hours were read from OCR text and not checked against the page images [TBC]. The 1(f) and 1(g) plates disagree at Bhagalpur (about 240–280 mm against 280–320 mm), which the 5-km rule of (c) resolves by taking the higher. No storm-drain DPR for any Bihar city, with its design return period and rainfall analysis, was found for this Manual [TBC], so the design basis of the drainage works now being built in Patna and other cities could not be compared with this clause.
2.4 Design return periods (summary)
2.4.1 Design AEPs are set in the chapters for each element. They are summarised here so that the correct rainfall is extracted at the start of design.
Table 2.1 — Design return periods (summary)
| Element | Design AEP (return period) | Check event | Chapter |
|---|---|---|---|
| Minor drains: Patna, Gaya, Bhagalpur, Muzaffarpur and Darbhanga core and high-density areas | 10% (10-yr) | 1% (100-yr) overland path | 6 |
| Minor drains: other Class I urban areas | 20% (5-yr) | 1% overland path | 6 |
| Minor drains: other areas | 50% (2-yr) | 1% overland path | 6 |
| Arterial roads and crossings | 2–4% (25–50-yr) | next higher AEP | 6 |
| Collector / local roads | 4% / 10% (25 / 10-yr) | 2% / 4% (50 / 25-yr), plus the 1% overland path | 6 |
| Major (overland) system | 1% (100-yr) | — | 6 |
| Retention volume | Percentile daily rainfall (Clause 2.10) | — | 4 |
| Detention: standard catchments | 50%, 10%, 1% (2, 10, 100-yr) | 1% emergency spillway | 4 |
| Detention: flood-sensitive catchments | Mixed-frequency rule, Clause 2.11 | 1% | 4 |
| Building floor levels | 1% + 0.5 m freeboard | — | 6 |
| Detention emergency spillway | 1% with outlet blocked | 0.2% (500-yr) where high hazard | 4 |
Commentary. These values exceed the CPHEEO (2019) national advisory minimums of 5-yr (Class I cities) and 2-yr (other areas). CPHEEO allows a State to set higher values. The values are set in Chapters 4 and 6, and the table is reproduced here for convenience.
2.5 Design durations
2.5.1 Conveyance elements (pipes, open drains, inlets, culverts) shall be designed with the intensity for a duration equal to the time of concentration (Tc) of the contributing area (Chapter 3). The minimum duration is 10 minutes.
2.5.2 Storage elements (detention, retention, tanks, pumped sumps) shall be checked for every duration in the set {1, 2, 3, 6, 12, 24, 48, 72 h}. The largest required storage or water level governs. The 24-, 48- and 72-hour storms are mandatory checks at every site, whatever the critical-duration result.
2.5.3 Tidally influenced outfalls. For storage draining to a tidally influenced outfall (Chapter 5), the 48- and 72-hour storms shall also be run with the tailwater boundary of Clause 2.12.
Commentary. Bihar's worst floods have come when a long wet spell meets a full river. In August 1975 the Sone rose for about five days before its waters and the Ganga's entered Patna (as reported); the Ganga at Gandhi Ghat set its highest recorded level in August 2016, and passed it in September 2026 in what was reported as the third prolonged flood spell of the season (CWC; as reported). The monthly records show how much rain a single month can bring: 995.8 mm at Motihari in July 1977, 926.6 mm at Sabour and 815.4 mm at Bhagalpur in August 1987, 925.2 mm at Forbesganj in September 1960, 922.0 mm at Purnea in September 1989 and 800.7 mm at Patna (A) in July 1987 (IMD). The Patna waterlogging of September 2019 followed about 210–226 mm in three to four days, not a single extreme hour (as reported). Behind the embankments and the sluices of the Ganga and the Punpun at Patna, where the drains are closed and pumped when the rivers are high, storage is filled by the whole wet spell, not by its peak hour. A rule based only on critical duration, applied to a small site, picks a 1–2 hour storm and misses this failure mode. That is why the long-duration checks are mandatory.
2.6 Sub-daily rainfall
2.6.1 Where NIH-DHAARA or an approved station IDF provides values directly for the required duration, those values shall be used.
2.6.2 Where only daily (24-hour) depths are available for a duration below 24 hours, the sub-daily depth shall be derived using the ratio set of Annex 2B. These are duration-to-24-hour ratios calibrated to Bihar recording gauges. They shall not be lower than the ratios of the CWC Flood Estimation Report for the subzone (1(d), 1(f) or 1(g)). IMD Das et al. (2022) has no Bihar station panel and is not used as a floor in Bihar.
2.6.3 Fixed-interval adjustment. Depths from fixed observation windows (for example 08:30–08:30 IST daily data, or clock-hour data) shall be converted to sliding-window ("true interval") depths:
- 1.13 for a single fixed observation interval;
- 1.04 for 2 intervals;
- 1.02 for 3–4 intervals.
This adjustment does not apply where the approved source already gives true-interval values.
2.6.4 The empirical relationship P(t) = P(24)·(t/24)^(1/3) shall not be used for design unless Annex 2B confirms it for the zone concerned.
Commentary. The one-third power rule is common in Indian project reports, but no primary IMD source for it was found during research for this Manual. It applies one fixed curve shape everywhere: P(1h)/P(24h) = 0.35, P(3h) = 0.50, P(6h) = 0.63 and P(12h) = 0.79. It cannot represent the difference between a short convective burst and a long SW monsoon soak, and it tends to understate short-duration depths in convective coastal storms. Annex 2B shall tabulate the NIH-DHAARA ratios P(t)/P(24h) against these values by zone. That comparison shows whether the rule is acceptable anywhere in the State and corrects older daily-based analyses. The fixed-interval factors are the standard WMO (Hershfield) values. The IMD 2022 study applies similar clock-hour to any-hour corrections.
2.7 Point, grid and areal rainfall
2.7.1 Design depths are point values. Where an approved source provides grid-average values (for example 0.25° cells), they shall be converted to point values with the grid-to-point factors in Annex 2C before use.
2.7.2 For catchments ≤ 10 km², ARF = 1.0.
2.7.3 For catchments > 10 km², apply ARF as follows:
- for 25–5,000 km² in subzone 1(d), 1(f) or 1(g): use the ARF curves of the applicable CWC Flood Estimation Report;
- for 10–25 km²: interpolate linearly between ARF = 1.0 at 10 km² and the CWC value at 25 km².
2.7.4 An ARF shall never be applied to storage design for a single development site.
Commentary. Gridded and district-average return levels are much lower than point values. For example, NIH-DHAARA's IMDAA cell at Gaya gives a 50-year 24-hour depth of about 227 mm, while the Gaya (A) gauge has recorded 290.8 mm (16 September 1976), and its cell at Patna about 288 mm, while gauges in and near the city have recorded 366.0 mm (Patna Observatory, 8 September 1918) and 498.9 mm (Dinapur, 25 June 1897) (NIH-DHAARA, queried 6 Nov 2026; IMD; CWC FER 1(d)). Over most of north Bihar the same product errs the other way: 362 mm at Darbhanga, against a station record of 266.7 mm in more than a century, and 526 mm at Kishanganj, against a plate value of about 320–360 mm. Single storms are patchy at a scale that no cell of about 12 km can show: in the 24 hours to 05:30 on 30 September 2019, Patna recorded 91 mm and Gaya 17 mm, while Rosera, Udaikishanganj, Baltara and Chargharia recorded more than 200 mm (IMD, as reported). Neither error can be corrected without the factors of Annex 2C. Using grid values as point values without correction would make site-level design unsafe.
2.8 Climate factor
2.8.1 Until a statewide future-climate rainfall product is adopted, present-day design depths shall be multiplied by the following interim climate factors:
Table 2.2 — Interim climate factors
| Duration | Climate factor (CF) |
|---|---|
| ≤ 6 h | 1.20 |
| > 6 h to 72 h | 1.10 |
2.8.2 The CF applies to all elements with a design life of more than 25 years. For temporary works (design life ≤ 5 years), CF = 1.0.
2.8.3 The climate factor does not apply to the retention depth (Clause 2.10) or to the water quality volume depth (Chapter 8). Those depths are percentile or frequent-event statistics of everyday rainfall, not AEP design values.
2.8.4 Where NIH-DHAARA, or a product adopted on review under Clause 2.14, provides projected future-climate depths, those depths shall replace the interim factors.
Commentary. CPHEEO (2019) considers a fixed climate factor "not feasible" nationally and recommends trend testing instead. That leaves designers without a usable number. The 1.20 short-duration factor matches the UK value cited by CPHEEO itself. It is at or below published projections for India: Ali and Mishra (2018) project 3-hourly 100-year maxima rising by about 20% at 1.5 °C and 25% at 2.0 °C of warming. No design uplift factor has been adopted in Bihar, and the rainfall projections of the State action plan on climate change were not found for this Manual [TBC]. Seasonal totals and extremes point different ways. Studies of the record from 1901 report falling annual and monsoon totals, especially in east Bihar after 1960, while a study of gridded data for 1901–2020 reports that monsoon daily rainfall intensity has risen considerably, particularly in north Bihar (both seen only through summaries; the metric of the second was not read [TBC]). Recent extremes have not fallen: Motihari recorded its highest day, 520.0 mm, on 25 August 2005, Muzaffarpur its highest, 436.0 mm, on 26 September 2007, and Ekma (Saran) 400.0 mm on 8 June 2005, all after the CWC plates of 1985–1994 were drawn (IMD). Half of the highest flood levels at the CWC sites of north Bihar were set in 2016–2025 (CWC), though river levels also reflect embankments, sediment and rain in Nepal. NIH-DHAARA offers a CMIP6 projection but no historical run of the same model, so no ratio of future to present depths can be formed; under Clause 2.3.6(k) it would serve only as a check. The factors of Table 2.2 are therefore interim values, not Bihar estimates.
2.9 Temporal patterns (design hyetographs)
2.9.1 Storms up to 24 hours. Use the nested alternating-block method:
- construct the storm from the same IDF relationship (after the climate factor), at time steps no longer than Tc/3 and no longer than 15 minutes;
- place the peak block at 50% of the storm duration.
2.9.2 48- and 72-hour storms (SW monsoon pattern). Construct as follows:
- (a) The total storm depth equals the design depth for the full duration (48 or 72 h).
- (b) The final 24 hours contain the 24-hour design depth for the same AEP, distributed by the alternating-block method of 2.9.1.
- (c) The remaining depth (total minus the 24-hour depth) is spread uniformly over the preceding 24 or 48 hours.
Figure 2.2 — (a) 24-hour alternating-block design storm; (b) 72-hour SW monsoon design storm with the 24-hour design depth on the final day. Illustrative depths only. Original drawing for this Manual. The alternating-block method follows Chow, Maidment & Mays, Applied Hydrology (1988), §14.4.
2.9.3 Other temporal patterns. Huff-type or mass-curve patterns derived from Bihar storms may be used instead of 2.9.1 and 2.9.2 only after they are published in Annex 2D. SCS Type I, IA, II and III distributions shall not be used.
2.9.4 Large catchments. For catchments of 25–5,000 km², the CWC Flood Estimation Report time-distribution curves may be used, and a sensitivity run with 2.9.1 shall be reported.
Commentary. The alternating-block storm embeds every shorter-duration design intensity in one hyetograph. That makes it conservative and consistent across durations. The 72-hour pattern puts the most intense day last. This reproduces the monsoon sequence of Bihar: by the time the largest falls arrive in July–September, the water table in the diara, the chaurs and the north Bihar plain is near the surface, the pokhars, tals and chaurs are full, and the Ganga, the Sone, the Punpun, the Burhi Gandak and the Bagmati, fed by rain over their catchments in Nepal and Jharkhand, may already have closed the sluices on the outfalls through their embankments. SCS distributions are excluded because they come from US convective and Gulf storm data and have no basis in Bihar records.
2.10 Retention rainfall depth
2.10.1 The retention design depth is the 24-hour rainfall depth not exceeded on 90% of days with rain (≥ 2.5 mm) in the long-term record, read from the zone value in Annex 2E.
2.10.2 The site must retain on site the runoff from this depth (Chapter 4). Retention earns a detention credit equal to the reduction in required detention storage found by routing with the retention in place (Clause 4.4.6). The credit is not the retained volume subtracted one-for-one.
Commentary. This follows the Kansas City Metro APWA 5600 (2025.01) Required Retention Volume concept and Georgia's 1.0-inch runoff reduction standard. Both are based on percentile storms. A percentile depth is a statistic of everyday rainfall, not an AEP value, so it is computed from the daily record rather than from the frequency curves.
2.11 Design storms for pre- and post-development comparison
2.11.1 Same storm for both scenarios. Pre- and post-development runs shall use the same design storms:
- same AEP, duration, temporal pattern and climate factor;
- same antecedent moisture condition (Clause 2.11.4).
The two runs differ only in land surface parameters and Tc.
2.11.2 Standard catchments. For each of the 50%, 10% and 1% AEP storms and each duration in Clause 2.5.2:
Q_post(T) ≤ 0.9 × Q_pre(T)
2.11.3 Flood-sensitive catchments (as listed in Chapter 4: the catchments of Patna behind the Ganga, the Sone and the Punpun, of Muzaffarpur on the Burhi Gandak and of Darbhanga between the Bagmati and the Adhwara group, and tal and chaur land, and any catchment notified by the authority). The mixed-frequency rule applies:
Q_post(1% AEP, 100-yr) ≤ Q_pre(10% AEP, 10-yr), and Q_post(50% AEP, 2-yr) ≤ Q_pre(50% AEP, 2-yr),
The post-development peak is checked for each duration in Clause 2.5.2. The caps are taken at the pre-development critical duration. The 10-yr cap is the largest pre-development 10-yr peak over all durations, and the 2-yr cap is the largest pre-development 2-yr peak over all durations. Each cap applies to every post-development duration.
2.11.4 Antecedent moisture. Use AMC III (wet conditions) for every design storm, whatever its duration, from 15 June to 30 September at a site in sub-area BR-A Gandak–Burhi Gandak plain, BR-B Mithila and Kosi plain or BR-C Seemanchal of Annex 2A, or on tal, chaur or diara land anywhere in the State, and in July and August at a site in sub-area BR-D South Bihar plain (Magadh–Bhojpur) or BR-E South-east Ganga fringe and plateau margin. At any other site or time, use AMC III for a design storm that follows, or contains, a 5-day rainfall total of more than 53 mm. Use AMC II (average conditions) for every other storm. AMC I is not used for design.
2.11.5 Pre-development condition. Pre-development is defined in Chapter 3: greenfield, open land in good condition for the mapped hydrologic soil group. Existing impervious cover is not counted as pre-development.
Commentary. Matching each site's post-development peak to its own pre-development peak does not protect the catchment. Denver's analysis found that 100% matching at every site still produced 106% of historic peak downstream, which led to the 90% rule. The mixed-frequency rule is stricter. It caps the 100-yr post-development release at what the undeveloped site produced in a 10-yr storm. Malaysia (DID 2008: all ARIs ≤ pre-development 2-yr) is a tropical precedent for this kind of cap. AMC III for long storms reflects that SW monsoon extremes arrive after weeks of rain. In Bihar the wetness of the ground differs across the State as much as the rainfall does. In the north Bihar plain and Seemanchal (BR-A, BR-B and BR-C) the water table lay about 1.5–5.7 m below ground before the monsoon in the district profiles of 2011, with a water table 1.5 m below ground in a pit at Supaul in November (CGWB, as reported); chaurs and mauns hold water through the season; and the north-east is wet from the onset in mid-June, with June normals of 266.8–374.7 mm at Araria, Purnea and Kishanganj (IMD). The diara land of the Ganga and the Kosi is flooded each monsoon, and the Mokama group of tals, about 1,062 km² in Patna, Nalanda and Munger districts, is waterlogged through it (NIH, as reported). In the south Bihar plain (BR-D) and the south-east fringe and plateau margin (BR-E), June is drier, 116.4 mm at Patna and 133.2 mm at Gaya, while the July and August normals are 238.0–304.9 mm at Patna and 248.9–267.7 mm at Gaya (IMD). This Manual therefore uses AMC III from 15 June to 30 September in BR-A, BR-B and BR-C and on tal, chaur and diara land anywhere, in July and August in BR-D and BR-E, and at any other site or time only after a 5-day total of more than 53 mm, the NRCS growing-season threshold for AMC III; AMC II otherwise (Clause 2.11.4). These are interim choices set by this Manual; no study in the State has yet validated AMC classes against observed runoff.
Illustrative scale of the mixed-frequency rule. The values below are not design values. They assume a 2 ha site in a low-lying colony in south Patna behind the Punpun with 24-h depths of 200 mm (10-yr) and 350 mm (100-yr), SCS-CN runoff with Ia = 0.2S, and CN 70 pre-development and CN 92 post-development:
Table 2.3 — Illustrative scale of the mixed-frequency rule (not design values)
| Case | Runoff depth | Runoff volume (2 ha) |
|---|---|---|
| Pre-development, 10-yr 24 h | 111 mm | 2,210 m³ |
| Post-development, 100-yr 24 h | 325 mm | 6,500 m³ |
The post-development 100-yr storm generates about three times the runoff volume of the pre-development 10-yr storm. A peak-rate cap at the pre-development 10-yr level means most of the difference must be stored and released slowly, so storage of the order of 0.2 m³ per m² of site may be needed. For this reason the rule applies only in flood-sensitive catchments (Clause 2.11.3); elsewhere the 0.9 × Q_pre rule of Clause 2.11.2 applies.
2.12 Joint occurrence with tailwater
2.12.1 For outfalls under tidal or river backwater influence, the design rainfall of this chapter shall be combined with the tailwater conditions of Chapter 5 as follows. The more severe case governs.
- (a) Design rainfall (AEP as required) with a mean high water springs (MHWS) tailwater plus the sea-level allowance.
- (b) A 10% AEP (10-yr) 48-hour storm with the 1% AEP still-water level (tide plus surge) plus the sea-level allowance.
Bihar has no coast, so no outfall in the State is tidal and cases (a) and (b) do not arise. The tailwater is the river into which a city drains, and the nalas, tals and chaurs that local drains discharge into. For an outfall under river backwater, the site storm is combined with the river level under Clause 5.8.4, which pairs a design event on one side with a 10-yr event on the other in the same way as case (b). The river stage is read at the nearest CWC gauge. In the CWC bulletin of 31 October 2026 the danger level and highest flood level (HFL) are 48.60 m and 50.52 m (2016) for the Ganga at Gandhi Ghat and 50.45 m and 52.52 m (1975) at Dighaghat, in Patna; 50.60 m and 53.91 m (1976) for the Punpun at Sripalpur, into which the drains of south Patna outfall; 52.00 m and 53.79 m (1976) for the Sone at Maner; 52.53 m and 54.29 m (1987) for the Burhi Gandak at Sikandarpur, Muzaffarpur; 45.72 m and 48.96 m (1987) for the Bagmati at Hayaghat, Darbhanga; 35.65 m and 38.20 m (2017) for the Mahananda at Dhengraghat, Purnia; and, on the Ganga, 60.32 m and 62.09 m (1948) at Buxar, 41.76 m and 43.52 m (2021) at Hathidah, 39.33 m and 40.99 m (1976) at Munger and 33.68 m and 34.86 m (2021) at Bhagalpur (CWC). Press reports give 50.53–50.57 m at Gandhi Ghat on 5–6 September 2026, above the HFL that the bulletin still lists; the conflict is unresolved [TBC]. These HFLs lie 1.2–3.3 m above the danger levels, so an outfall below the HFL can be shut for days. When the rivers are high the sluices on Patna's outfalls to the Ganga and the Punpun are closed and runoff is lifted by the sump houses, reported as 56 permanent and 28 temporary drainage pumping stations in a Rajya Sabha reply of 27 November 2024 whose scope, Patna or the State, is unclear; so storage and pumps are checked for the gates-shut condition, with the local storm falling before, during or after the river peak. No document found in research for this Manual sets a design river level for the outfalls of any city in the State [TBC], and Chapter 5 sets the interim rule. Every level is stated on a named datum, as Chapter 5 requires; the datum of the CWC gauge levels quoted here is to be confirmed [TBC].
Commentary. Bihar has no coast, so no outfall is tidal and there is no storm surge; the coincident load is the stage of the rivers. The coincidence is on record. In August 1975 the Sone and the Ganga rose together and their waters entered Patna (as reported). In September 2026, during heavy rain, the Ganga at Gandhi Ghat rose above its highest recorded level, the sluice gates on the Ganga and the Punpun at Patna were closed and drains connected to the Ganga were blocked (as reported). The rivers stay high for days and weeks: on 31 October 2026, a month after that flood, the Ganga at Gandhi Ghat still stood at 45.41 m and the Punpun at Sripalpur at 46.68 m (CWC). Their floods come largely from rain over catchments far upstream, in Nepal and Jharkhand, so they give no warning of a local storm that falls while the gates are shut. Behind the embankments and sluices of Patna, Muzaffarpur and Darbhanga, the drains cannot outfall by gravity while the river is high and depend on pumps. The levels of the sources are on different datums, which is why Chapter 5 requires every level to name its datum. Because rainfall and surge share a weather cause (in Bihar, which has no coast, the counterpart of surge is the stage of the rivers, raised by the same monsoon systems that bring the heaviest rain to the cities and to the catchments above them in Nepal and Jharkhand: in August 1975 the Sone and the Ganga rose together and their waters entered Patna, and in September 2026 the Ganga at Gandhi Ghat rose above its highest recorded level during heavy rain, both as reported), they cannot be treated as independent. Case (b) is a simple joint-probability surrogate until a statistical joint analysis is adopted.
2.13 Submittal requirements
Every hydrologic submittal shall include a Design Rainfall Sheet (Form 2-1) stating:
- the site coordinates and zone;
- the source (Clause 2.3), version or access date, and a screenshot or export of the values extracted;
- a depth table for each AEP and duration used, before and after the fixed-interval factor, grid-to-point factor, ARF and climate factor;
- the cross-check values of Clause 2.3.3 and the floor check;
- the hyetographs used, as a table and a plot, for each design storm; and
- the AMC and pre-development definition adopted.
Figure 2.3 shows the steps of this chapter in the order in which the sheet records them.
Figure 2.3 — From design rainfall source to design storm: the steps a designer follows (source, AEPs and durations, point depth, grid-to-point and areal reduction, climate factor, temporal pattern, design storm), the clause that governs each step, what Form 2-1 records, and the separate route for the retention depth. Schematic. Original drawing for this Manual.
2.14 Review and update
2.14.1 The approving authority shall review this chapter every 10 years. It shall also review it within 2 years of any event in which recorded rainfall exceeds the 1% AEP 24-hour or 72-hour design depth at two or more approved gauges in the State.
2.14.2 Updates to NIH-DHAARA take effect for new submittals 6 months after release, unless the authority notifies otherwise.
References (chapter)
- National Institute of Hydrology, Roorkee. NIH-DHAARA: Design Hydrology and Advanced Rainfall Analysis. http://www.nihdhaara.in/
- Das, S.K. et al. (2022). Isopluvial analysis and intensity–duration–frequency curves for different cities in India. MAUSAM 73(4), 887–898. https://metnet.imd.gov.in/docs/mausamdocs/173412_F.pdf
- Central Water Commission (1987). Flood Estimation Report for Sone Subzone 1(d), Report No. S/15/1987, CWC Publication No. 33/88, Aug 1987, approved at the 46th meeting of the Planning and Co-ordination Committee, 27–28 Aug 1987 (Plates 8–10, of which Plate 9 is titled the 50-year and Plate 10 the 100-year map, although the text calls Plate 10 the 50-year map; the SUH relationships, p. 40, where the exponent of the tp relation is printed 1.102 in the table and 1.012 in the worked example; the short-duration ratio table, p. 50, whose 18-hour value was read from OCR text [TBC]; Annexure II; read from the Wayback Machine capture of 12 Apr 2016 of the cwc.gov.in copy). https://cwc.gov.in/regional-flood-estimation-report
- Central Water Commission (1985). Flood Estimation Report for Middle Ganga Plains Subzone 1(f), Report No. GP/10/1984, Oct 1985, approved at the 41st meeting of the Planning and Co-ordination Committee, 30 Jan 1985 (Plates 8 and 9, the SUH relationships, the short-duration ratio table, Fig. 10, whose 2-, 4- and 5-hour ratios were read from an OCR and not checked against the page image [TBC], and the worked example for Bridge No. 152 on the Muzaffarpur–Sagauli section; Wayback Machine capture of the cwc.gov.in copy). https://cwc.gov.in/regional-flood-estimation-report
- Central Water Commission (1994). Flood Estimation Report for Lower Ganga Plains Subzone 1(g) (revised), Design Office Report No. LG-1(g)/R-1/23/94, Nov 1994 (Plate 9, the short-duration ratio table, and Annexes 4.3 and 4.4, including the recording-gauge maxima at Sabour and Jamui; Wayback Machine capture of 12 Apr 2016 of the cwc.gov.in copy). https://cwc.gov.in/regional-flood-estimation-report
- MoHUA / CPHEEO (2019). Manual on Storm Water Drainage Systems, Part A.
- India Meteorological Department. Extremes of Temperature and Rainfall for Indian Stations (up to 2012), stations of Bihar (pp. M32–M38). https://imdpune.gov.in/library/public/EXTREMES%20OF%20TEMPERATURE%20and%20RAINFALL%20upto%202012.pdf
- India Meteorological Department (2011). Climate of Bihar. Climatological Summaries of States Series No. 18, Nov 2011 (district normals 1951–2000, Table V; storms and depressions 1891–2010, Table VII; heaviest 24-hour rainfall by district). https://mausam.imd.gov.in/patna/mcdata/climateofbihar.pdf
- India Meteorological Department (2020). New normal dates of onset/progress and withdrawal of the southwest monsoon over India (Pai et al.), press release of 15 May 2020, Table 2. https://internal.imd.gov.in/press_release/20200515_pr_804.pdf
- National Institute of Hydrology, Roorkee. NIH-DHAARA IDF Curve Tool (IMDAA reanalysis), queried at 16 cells in Bihar on 6 Nov 2026. http://117.252.14.251:8080/
- National Institute of Hydrology, Regional Centre, Patna. Characteristics of short interval rainfall in Punpun basin, Bihar (research report; seen only through a summary, not obtained [TBC]). https://oldiwp.indiawaterportal.org/articles/characteristics-short-interval-rainfall-punpun-basin-bihar-research-report-national
- Kathuria, S.N., Kaur, S. & Mehra, A.K. (1987). Rainfall intensity for local drainage design in Lucknow and its neighbouring area. MAUSAM 38(1), 85–88 (Tables 2–4; the basis of the floors of Clause 2.3.6(h)). https://mausamjournal.imd.gov.in/index.php/MAUSAM/article/download/2654/2468
- Central Water Commission, Lower Ganga Division-2, Patna. Daily water level and flood forecast bulletin, 31 Oct 2026 (via FMISC; read from the page image; datum to be confirmed [TBC]); and Water Resources Department, FMISC, Daily Flood Information Bulletin, 31 Oct 2026. https://www.fmiscwrdbihar.gov.in/bulletin/CWC_Bulletin.pdf ; https://www.fmiscwrdbihar.gov.in/bulletin/Flood%20Bulletin.pdf
- Rajya Sabha. Reply of 27 Nov 2024 on drainage pumping stations in Bihar (seen only through a search summary). https://rsdebate.nic.in/bitstream/123456789/754718/1/PQ_266_27112024_S10_p23_p25.pdf
- Central Ground Water Board. District groundwater profiles of Supaul, Saharsa, Katihar and Sitamarhi (2011) (seen only through search summaries).
- Studies of rainfall trends in Bihar: Hydrology (MDPI, 2024), gridded data 1901–2020 (summary read); Current World Environment 18(2) and 20(1) (summaries read). https://doaj.org/article/69bb222448444c808df7ab0c9320a2e0 ; https://www.cwejournal.org/pdf/Vol20No1/CWE_Vol20_No1_p_105-120.pdf
- Ali, H. & Mishra, V. (2018). Increase in subdaily precipitation extremes in India under 1.5 and 2.0 °C warming worlds. Geophysical Research Letters 45. https://repository.ias.ac.in/142345
- Press reports of the Patna rain of September 2019 and July 2025, the monsoon withdrawal of 2025 and the Ganga at Patna in September 2026 (secondary sources). https://www.pressreader.com/india/hindustan-times-lucknow/20191001/281797105729423 ; https://www.cbsnews.com/news/monsoon-season-flooding-india-heavy-late-rains-kills-more-than-100-in-several-days-2019-09-30 ; https://www.patrika.com/en/state-news/patna-breaks-28-year-old-rainfall-record-city-inundated-19820889 ; https://patnapress.com/bihar-monsoon-withdrawal-2025-31-percent-deficit/ ; https://theprint.in/india/ganga-water-level-breaches-highest-flood-mark-at-patnas-gandhi-ghat-amid-heavy-rain/3034353/
- Chow, V.T., Maidment, D.R. & Mays, L.W. (1988). Applied Hydrology. McGraw-Hill (alternating-block method, §14.4).
- Kansas City Metro Chapter APWA (2025). Section 5600 Storm Drainage Systems and Facilities, Version 2025.01.
- Mile High Flood District (Denver). Urban Storm Drainage Criteria Manual (90% release rationale).
- Department of Irrigation and Drainage Malaysia (2008, 2012). Urban Stormwater Management Manual (MSMA).
Annexes
| Annex | Content |
|---|---|
| 2A | NIH-DHAARA vs IMD station and IMD gridded checks at benchmark points; zone map |
| 2B | Sub-daily ratios P(t)/P(24h) by zone: NIH-DHAARA (hourly-based) vs the one-third rule |
| 2C | Grid-to-point factors |
| 2D | Bihar temporal patterns (Huff curves) |
| 2E | Retention percentile depths by zone |
| Form 2-1 | Design Rainfall Sheet |
Commentary. Most past drainage failures in Bihar trace to the rainfall input, not the hydraulics. Bihar shows how. No published Bihar document sets a design storm, return period or rainfall intensity for a city's storm drains: none was found in the material of BUIDCO, PMC and the Patna Master Plan 2031 searched for this Manual, and the drainage DPR for Danapur, Khagaul and Phulwari is known only from the press. The rainfall figures that circulate after a flood are often unsourced: a press report that 175.4 mm on 29 July 2025 broke Patna's record of 181.1 mm from 1997 contradicts itself, and IMD's own record for June 1997 at Patna (A) is 205.4 mm (IMD). The two published sources that seem to fill the gap do not. IMD Das et al. (2022) has no panel for any station in Bihar, and NIH-DHAARA's reanalysis-based depths are too high over most of north Bihar, too low at Gaya, and low at 1 hour everywhere (Clause 2.3.6). The CWC Flood Estimation Reports are the only regional sub-daily source, and the three subzones that meet in the State give 1-hour ratios that differ by about a fifth across the Ganga at Patna. Fixing one transparent source and method for the whole state is the main purpose of this chapter.