Annexes to Chapter 6Minor and Major Drainage Systems
These annexes support Chapter 6. Annex 6A (standard inlets and their capacity curves) and Annex 6B (sediment yield) need test and survey data that are not yet available; each states what it will contain and the interim rule to use until it is published. Annex 6C gives standard drawings that carry only the dimensions Chapter 6 and Chapter 9 already set; every other dimension is marked "to be confirmed in design". Form 6-1 is a draft form: it lists what Clause 6.15 requires and does not add to it.
Annex 6A — Standard inlet types for Uttar Pradesh with capacity curves (on grade and sag)
Supports Clauses 6.6.1 to 6.6.7 of Chapter 6 and Clause 9.11 of Chapter 9.
To be prepared. This annex will contain a short list of standard inlet types for Uttar Pradesh streets (kerb-opening, grate and combination inlets, including the road-level wall opening into a covered drain) and, for each type, capacity curves on grade and in a sag. It needs a fixed set of standard inlet geometries agreed with the road-owning agencies, and rating tests of those geometries (laboratory or full-scale), or HEC-22 calculations for each geometry checked against tests (data and likely sources: Public Works Department (PWD), NHAI and Lucknow Municipal Corporation (Nagar Nigam Lucknow) standard details, IIT Kanpur, IIT (BHU) Varanasi, MNNIT Allahabad or other hydraulic laboratories, manufacturers' tested ratings). Until it is published, compute the clean capacity of the inlet actually proposed by the methods of FHWA HEC-22 (4th edition, 2024) or from the manufacturer's tested rating for that exact geometry (Clause 6.6.2), reduce it by the clogging factors of Table 6.5 (Clause 6.6.3), and meet the interim requirements of Table 6A.1.
Table 6A.1 — Interim requirements for inlets until Annex 6A is published (from Chapters 6 and 9)
| Item | Requirement | Clause |
|---|---|---|
| Inlet type on public streets | Kerb-opening or combination inlets, unless the Approving Authority accepts grate-only inlets for a location | 6.6.1(a) |
| Inlet level | Openings at road level; gutter depression where practicable | 6.6.1(b) |
| Clean capacity | FHWA HEC-22 (4th ed., 2024) or the manufacturer's tested rating for the exact geometry; CPHEEO §5.6.2 equations as a cross-check only | 6.6.2 |
| Clogging, on grade | Grate 50%; kerb opening 10% | 6.6.3, Table 6.5 |
| Clogging, in a sag | Grate 50%; kerb opening 20% | 6.6.3, Table 6.5 |
| Spacing | By sequential calculation from the top of each gutter run; not more than 30 m on kerbed roads | 6.6.4 |
| Kerb opening size | Clear height at least 100 mm; length at least 1.0 m | 9.11.4 |
| Grate pattern | Openings parallel to the direction of travel not wider than 25 mm | 9.11.3(a) |
| Load class | D400 in carriageways and medians; C250 within 0.5 m of the kerb; B125 in footpaths and cycle tracks (or the equivalent IS class) | 9.11.2 |
| Connection pipe | At least 300 mm diameter; gradient giving at least 0.9 m/s at the inlet's design flow | 6.6.6 |
| Silt sump | At least 300 mm deep below the outlet pipe invert, cleanable from the surface | 6.6.7, 9.11.6 |
The intended layout of the annex is given in Tables 6A.2 to 6A.4.
Table 6A.2 — Register of standard inlet types (layout)
| Type code | Description | Grate size or kerb opening (mm) | Gutter depression (mm) | Load class | Standard drawing |
|---|---|---|---|---|---|
| ______ | ______ | ______ | ______ | ______ | ______ |
| ______ | ______ | ______ | ______ | ______ | ______ |
Table 6A.3 — Capacity on grade (layout; one table per inlet type)
| Cross slope Sx (m/m) | Longitudinal slope SL (m/m) | Gutter flow Q (L/s) | Spread T (m) | Clean intercepted flow (L/s) | Design intercepted flow after clogging (L/s) | Bypass flow (L/s) |
|---|---|---|---|---|---|---|
| ______ | ______ | ______ | ______ | ______ | ______ | ______ |
| ______ | ______ | ______ | ______ | ______ | ______ | ______ |
Table 6A.4 — Capacity in a sag (layout; one table per inlet type)
| Ponded depth at the inlet (mm) | Clean capacity (L/s) | Clogging factor (Table 6.5) | Design capacity (L/s) | Flow regime (weir, orifice or transition) |
|---|---|---|---|---|
| ______ | ______ | ______ | ______ | ______ |
| ______ | ______ | ______ | ______ | ______ |
Annex 6B — Sediment yield for silt-trap sizing and calibration of the sediment allowance
Supports Clauses 6.7.4, 6.7.8, 6.13.3 and 6.13.10 of Chapter 6.
To be prepared. This annex will contain sediment yields for urban drains in Uttar Pradesh, by land use and drain type, for sizing the silt traps of Clause 6.13.3, and a calibration of the sediment allowance of Clause 6.7.8 against measured silt depths. It needs desilting records (volume or mass removed per drain length and per catchment area, with dates), silt-depth surveys before and after the south-west monsoon, and catchment land-use and soil data (data and likely sources: desilting records of Lucknow Municipal Corporation (Nagar Nigam Lucknow) and other urban local bodies, I&WRD records for channels, land cover from NRSC, soils from the Uttar Pradesh soil survey and NBSS&LUP, rainfall from IMD). Until it is published, size each silt trap from the designer's stated estimate of the sediment expected between scheduled cleanings, based on the desilting records of the same drain or of similar drains in the same local body, and state the cleaning interval assumed; the interval shall not be longer than the yearly pre-monsoon desilting of Clause 6.13.10. Inlet silt sumps remain at least 300 mm deep (Clause 6.6.7), and the sediment allowance of Clause 6.7.8 applies unchanged.
The intended method is a simple volume balance, with every term to be stated in the design:
V_trap = Y · A · t_c
where V_trap is the sediment storage volume of the trap below its outlet invert (m³), Y is the sediment yield for the catchment's land use and drain type (m³/ha per year, from Table 6B.2 once published), A is the catchment area draining to the trap (ha), and t_c is the scheduled cleaning interval (years). The annex will state whether a safety margin is added.
Table 6B.1 — Sediment allowances already set by Chapter 6 (provisional, to be calibrated)
| Element | Sediment allowance at the invert | Clause |
|---|---|---|
| Open and covered drains | Greater of 75 mm and 10% of the clear internal depth | 6.7.8(a) |
| Pipes of 600 mm diameter or more | 5% of the internal diameter | 6.7.8(b) |
| Pipes below 600 mm | No allowance; minimum velocity of Clause 6.7.3(a) applies | 6.7.8(c) |
| Drains and pipes that cannot reach the minimum velocity | Allowance doubled; mechanical desilting access provided | 6.7.4(b), (c) |
| Inlet silt sumps | At least 300 mm below the outlet pipe invert | 6.6.7 |
Table 6B.2 — Sediment yield by land use and drain type (layout)
| Land use or catchment type | Drain type | Sediment yield Y (m³/ha per year) | Bulk density (t/m³) | Local body and records used | Years of record |
|---|---|---|---|---|---|
| ______ | ______ | ______ | ______ | ______ | ______ |
| ______ | ______ | ______ | ______ | ______ | ______ |
Table 6B.3 — Calibration of the sediment allowance (layout)
| Drain or pipe ID | Clear internal depth or diameter (mm) | Allowance under Clause 6.7.8 (mm) | Measured silt depth before pre-monsoon desilting (mm) | Measured silt depth at the end of the monsoon (mm) | Ratio of measured to allowance |
|---|---|---|---|---|---|
| ______ | ______ | ______ | ______ | ______ | ______ |
| ______ | ______ | ______ | ______ | ______ | ______ |
Annex 6C — Standard drawings: covered roadside drain with removable covers, access chamber, inlet with silt sump
Supports Clauses 6.6, 6.7.6 to 6.7.10 and 6.13 of Chapter 6, and Clauses 9.11 and 9.12 of Chapter 9.
The drawings below are schematic standard drawings. They show only the dimensions that Chapter 6 and Chapter 9 set. Wall and slab thicknesses, reinforcement, concrete grade and cover, chamber plan sizes and frame details are to be confirmed in design: they come from the structural design (Clause 9.1.2) and the exposure class of Clause 9.13. Table 6C.1 lists the dimensions shown and their source clauses.
Figure 6C.1 — Standard drawing: covered roadside drain with removable covers, kerb inlets at road level, footpath slots, freeboard to the soffit and sediment allowance, with a plan of cover panels and access chambers along the footpath. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), Chapter 5, and IRC:SP:50-2013.
Figure 6C.2 — Standard drawing: access and junction chamber on a covered drain, with the clear opening, junction width, entry angle of the incoming drain, outgoing invert below the chamber floor, and cover requirements. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), §5.3.4 and Chapter 11.
Figure 6C.3 — Standard drawing: kerb inlet at road level with silt sump, connection pipe and cover, and an elevation of the kerb opening. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), Figure 5.9, and FHWA, HEC-22 Urban Drainage Design Manual (4th ed., 2024).
Table 6C.1 — Dimensions on the standard drawings and their source clauses
| Drawing | Item | Dimension or rule | Clause |
|---|---|---|---|
| 6C.1 | Clear internal size of a covered public drain | At least 0.6 m wide and 0.6 m deep | 6.7.6(c) |
| 6C.1 | Freeboard to the cover soffit | Table 6.7; not less than 150 mm for any roadside drain | 6.7.9, 6.13.1(a) |
| 6C.1 | Sediment allowance | Greater of 75 mm and 10% of clear depth | 6.7.8(a) |
| 6C.1 | Removable cover panels | At not more than 10 m centres; each at least 0.6 m long and spanning the full clear width; recessed lifting points; flush with the footpath | 6.13.2(a) |
| 6C.1 | Footpath runoff | Through slots or grated openings in the cover | 6.13.1(c) |
| 6C.1 | Kerb inlets | Openings in the drain wall at road level, each with a silt sump; spacing by calculation, not more than 30 m | 6.13.1(b), 6.6.4 |
| 6C.1, 6C.2 | Access chambers | At every junction, bend and change of section, and at not more than 30 m centres on straight runs | 6.13.2(b) |
| 6C.2 | Clear access opening | At least 0.6 m × 0.6 m (600 mm) | 6.13.2(b), 9.12.3 |
| 6C.2 | Junction chamber | Internal width at least twice the outgoing drain width; incoming drains at less than a right angle; outgoing invert below the chamber floor | 6.7.10(b) |
| 6C.2 | Covers | Load class for the location; hinged or locked; bolted or locked where the 1% AEP HGL can rise above the cover | 9.11.2, 9.11.5, 9.12.6 |
| 6C.2 | Cleaning | By machine from the surface; ladders, where provided, corrosion-resistant and encapsulated | 9.12.7 |
| 6C.3 | Kerb opening | At road level; clear height at least 100 mm; length at least 1.0 m | 6.6.1(b), 9.11.4 |
| 6C.3 | Silt sump | At least 300 mm below the outlet pipe invert; emptied by suction or grab machine | 6.6.7, 9.11.6 |
| 6C.3 | Connection pipe | At least 300 mm diameter; at least 0.9 m/s at the design flow | 6.6.6 |
| 6C.3 | Grate in a combination inlet | Openings parallel to travel not wider than 25 mm; Table 6.5 clogging on each part | 9.11.3, 6.6.3 |
| All | Wall and slab thickness, reinforcement, concrete grade and cover, chamber plan size, gutter depression depth | To be confirmed in design | 9.1.2, 9.13 |
Form 6-1 — Conveyance Design Report checklist
Supports Clause 6.15 of Chapter 6.
Draft form — Uttar Pradesh Stormwater Design Manual, Draft v1.0. Not for statutory use.
Attach this checklist to the front of the Conveyance Design Report. For each item, enter Yes, No or Not applicable, and the drawing or page where it is shown.
Section A — Project
Table 6F.1 — Form 6-1, Section A: project
| Field | Entry |
|---|---|
| Project name and location | ______ |
| Local body, and Tier A or Tier B (Chapter 1) | ______ |
| Applicant | ______ |
| Designer (name and registration) | ______ |
| Total catchment area served (ha) | ______ |
| High-density area status for the 10% AEP minor system (Clause 6.4.4) | ______ |
| Within the coastal band of Clause 6.11.6 (Yes / No) | ______ |
| Date and revision | ______ |
Section B — Contents required by Clause 6.15
Table 6F.2 — Form 6-1, Section B: contents required by Clause 6.15
| No. | Item | Clause | Provided (Yes / No / NA) | Drawing or page |
|---|---|---|---|---|
| 1 | Catchment plan: sub-catchments, minor system, inlet locations and the 1% AEP major-system overland flow paths | 6.3.2 | ||
| 2 | Land-use and road-class AEP adopted for each element, and the high-density area status | Table 6.1, 6.4.4 | ||
| 3 | Design flows, with the rainfall sheet of Chapter 2 and the method of Chapter 3 | 6.3.4 | ||
| 4 | Gutter spread, depth and D·V checks for the minor, check and 1% events | Tables 6.2, 6.3 | ||
| 5 | Inlet schedule: clean capacity, clogging factor, design capacity and bypass flow | 6.6 | ||
| 6 | Pipe and drain design tables: n, velocity, sediment allowance and freeboard | 6.7 | ||
| 7 | HGL profiles for the minor and check events, with the tailwater used | 6.8 | ||
| 8 | Sag ponding levels, including the fully-blocked check | 6.10 | ||
| 9 | Floor-level schedule for every building | 6.11 | ||
| 10 | Culvert and crossing calculations (with Form 9-1) | 6.12, Chapter 9 | ||
| 11 | Utilities-crossing schedule and access-opening layout for covered drains | 6.13 |
Section C — Design basis
Table 6F.3 — Form 6-1, Section C: design basis
| Field | Entry | Clause |
|---|---|---|
| Minor-system design AEP adopted | ______ | Table 6.1 |
| Road class(es) and design / check AEPs for road drainage and crossings | ______ | Table 6.1, 6.4.2 |
| Rainfall source and climate factor applied | ______ | 6.3.4, Chapter 2 |
| Method: Rational Method (catchment ≤ 16 ha, single element) or hydrograph method with routing | ______ | 6.3.4(a), (b) |
| Minimum time of concentration used (not less than 10 min) | ______ | 6.3.4(c) |
| Tailwater at the outfall for the HGL (MHWS + 0.3 m at tidal outfalls, or the receiving level) | ______ | 6.8.2 |
| Any transfer of flow between natural catchments (none unless accepted under 6.3.5) | ______ | 6.3.5 |
Section D — Compliance checks
Table 6F.4 — Form 6-1, Section D: compliance checks
| No. | Check | Limit | Clause | Complies (Yes / No / NA) |
|---|---|---|---|---|
| D1 | Every inlet, sag, pipe, drain, culvert and storage element has a 1% AEP overland path | Shown on plan | 6.3.2 | |
| D2 | Major-system flow = 1% AEP peak less the clogged minor-system capacity | Computed at each point | 6.3.3 | |
| D3 | Spread in the minor event | Table 6.2 | 6.5.2 | |
| D4 | Depth in the check and 1% events | ≤ 150 mm at the crown; ≤ 350 mm at the deepest point | Table 6.2 | |
| D5 | Flow hazard (D·V) by location | Table 6.3 | 6.5.3 | |
| D6 | Inlet clogging factors applied | Table 6.5 | 6.6.3 | |
| D7 | Inlet spacing on kerbed roads | ≤ 30 m | 6.6.4(a) | |
| D8 | Sag inlet design capacity ≥ minor design flow arriving; flanking inlets where required | — | 6.6.5 | |
| D9 | Inlet connection pipes and silt sumps | ≥ 300 mm dia, ≥ 0.9 m/s; sump ≥ 300 mm | 6.6.6, 6.6.7 | |
| D10 | Manning's n not less than the minimum design values | Table 6.6 | 6.7.2 | |
| D11 | Minimum velocity at the minor design flow | 0.6 m/s drains; 0.9 m/s pipes | 6.7.3(a) | |
| D12 | Maximum velocity and Froude number | 3.0 m/s lined drains and pipes; Fr ≤ 0.8 | 6.7.3(b), (d) | |
| D13 | Where minimum velocity cannot be met: velocity reported, sediment allowance doubled, desilting access provided | — | 6.7.4 | |
| D14 | Pipes sized for pipe-full capacity, not the 0.95-depth peak | — | 6.7.5 | |
| D15 | Minimum sizes | Pipes 300 mm (450 mm public mains); open drain bed 0.3 m; covered public drains 0.6 m × 0.6 m | 6.7.6 | |
| D16 | Cover to pipes; flotation check where groundwater is within 1 m of the crown | ≥ 0.6 m; ≥ 0.9 m under carriageways | 6.7.7 | |
| D17 | Sediment allowance in capacity | 6.7.8 values | 6.7.8 | |
| D18 | Freeboard, including superelevation at bends | Table 6.7 | 6.7.9 | |
| D19 | Bend radii and junction sumps | 6.7.10 | 6.7.10 | |
| D20 | Manhole spacing on straight runs | Table 6.8 | 6.7.11 | |
| D21 | HGL below inlet rims and manhole covers in the minor event | ≥ 0.3 m | 6.8.3 | |
| D22 | Manholes that can surcharge above ground: bolted or locked covers | — | 6.8.4 | |
| D23 | Soffits matched or outgoing soffit lower; outgoing invert not above the lowest incoming invert | — | 6.8.6 | |
| D24 | Gate and valve losses included in the HGL; non-return valves on private connections where required | — | 6.8.7, 6.8.8 | |
| D25 | Overland flow paths outside streets: width, tenure, no obstruction, continuous fall | ≥ 1% top width + 0.5 m each side, ≥ 3.0 m | 6.9.2 | |
| D26 | Compound walls across mapped flow paths: openings pass the 1% flow at 50% blockage | — | 6.9.3 | |
| D27 | Access strip along open drains with top width ≥ 2 m | ≥ 3.5 m, linked to a road at ≤ 500 m | 6.9.4 | |
| D28 | Drainage reserve where required: width, separate plot, no structures, markers, services, 2 m stability check | Table 6.9 | 6.9.6–6.9.8 | |
| D29 | Sag ponding in the 1% event, overflow route, and fully-blocked check | ≤ 350 mm at the deepest point | 6.10.2, 6.10.3 | |
| D30 | Trapped sags and road underpasses | 6.10.4, 6.10.5 | 6.10.4, 6.10.5 | |
| D31 | Floor levels | ≥ 1% AEP level + 0.5 m; defaults of 6.11.3 where no level is computed | 6.11.1–6.11.3 | |
| D32 | Basements and building services | 6.11.4, 6.11.5 | 6.11.4, 6.11.5 | |
| D33 | Coastal band: floor ≥ 1% still-water level + 2 × SLA (+ wave set-up where applicable) + 0.5 m; no basement rooms or plant | — | 6.11.6 | |
| D34 | Culverts: design AEP, overtopping, 50% / 20% blockage check, minimum size | ≥ 900 mm | 6.12 | |
| D35 | Covered drains: removable panels and access chambers | ≤ 10 m; ≤ 30 m | 6.13.1, 6.13.2 | |
| D36 | Silt traps, screens with bypass and 50% blockage check | — | 6.13.3, 6.13.4 | |
| D37 | No building over drains; no utilities in the flow area or freeboard; existing crossings deducted with 50% blockage | — | 6.13.5, 6.13.6 | |
| D38 | No sewage connections; sealed joints next to sewers; edge protection on open drains deeper than 1.0 m | — | 6.13.7, 6.13.8 | |
| D39 | Outfalls: tailwater, flap gates or non-return valves below the 1% still-water level, outlet protection | — | 6.14 |
Section E — Variances
Table 6F.5 — Form 6-1, Section E: variances
| Clause | Requirement not met | Reason and proposed alternative | Approved by and date |
|---|---|---|---|
| ______ | ______ | ______ | ______ |
Section F — Signatures
The report shall be prepared and signed by a registered professional, and the Professional Design Certificate (Form 10-3) attached (Clauses 10.6.1 and 10.6.3 of Chapter 10). Where a structure stands within 2 m of the edge of a drainage reserve, the stability design shall also be signed by a qualified structural engineer (Clause 6.9.8(f)).
Table 6F.6 — Form 6-1, Section F: signatures
| Role | Name | Registration or empanelment no. | Signature | Date |
|---|---|---|---|---|
| Designer | ______ | ______ | ______ | ______ |
| Structural engineer (Clause 6.9.8(f), where applicable) | ______ | ______ | ______ | ______ |
Draft form — Uttar Pradesh Stormwater Design Manual, Draft v1.0.