Draft v1.0 prepared by NEER. Not adopted by the Government of Arunachal Pradesh or any authority, local body or community, and has no legal force. About this draft

Annexes to Chapter 6Minor and Major Drainage Systems

These annexes support Chapter 6. Annex 6A (standard inlets and their capacity curves) and Annex 6B (sediment yield) need test and survey data that are not yet available; each states what it will contain and the interim rule to use until it is published. Annex 6C gives standard drawings that carry only the dimensions Chapter 6 and Chapter 9 already set; every other dimension is marked "to be confirmed in design". Form 6-1 is a draft form: it lists what Clause 6.15 requires and does not add to it.


Annex 6A — Standard inlet types for Arunachal Pradesh with capacity curves (on grade and sag)

Supports Clauses 6.6.1 to 6.6.7 of Chapter 6 and Clause 9.11 of Chapter 9.

To be prepared. This annex will contain a short list of standard inlet types for Arunachal Pradesh streets (kerb-opening, grate and combination inlets, including the road-level wall opening into a covered drain) and, for each type, capacity curves on grade and in a sag. It needs a fixed set of standard inlet geometries agreed with the road-owning agencies, and rating tests of those geometries (laboratory or full-scale), or HEC-22 calculations for each geometry checked against tests (data and likely sources: Public Works Department (PWD), PWD (Highways) and Itanagar Municipal Corporation standard details, the engineering institutions of the State and the region, among them NERIST at Nirjuli, none of whose hydraulic testing capability was identified during research [TBC], or other hydraulic laboratories, manufacturers' tested ratings). Until it is published, compute the clean capacity of the inlet actually proposed by the methods of FHWA HEC-22 (4th edition, 2024) or from the manufacturer's tested rating for that exact geometry (Clause 6.6.2), reduce it by the clogging factors of Table 6.5 (Clause 6.6.3), and meet the interim requirements of Table 6A.1.

Table 6A.1 — Interim requirements for inlets until Annex 6A is published (from Chapters 6 and 9)

Item Requirement Clause
Inlet type on public streets Kerb-opening or combination inlets, unless the Approving Authority accepts grate-only inlets for a location 6.6.1(a)
Inlet level Openings at road level; gutter depression where practicable 6.6.1(b)
Clean capacity FHWA HEC-22 (4th ed., 2024) or the manufacturer's tested rating for the exact geometry; CPHEEO §5.6.2 equations as a cross-check only 6.6.2
Clogging, on grade Grate 50%; kerb opening 10% 6.6.3, Table 6.5
Clogging, in a sag Grate 50%; kerb opening 20% 6.6.3, Table 6.5
Spacing By sequential calculation from the top of each gutter run; not more than 30 m on kerbed roads 6.6.4
Kerb opening size Clear height at least 100 mm; length at least 1.0 m 9.11.4
Grate pattern Openings parallel to the direction of travel not wider than 25 mm 9.11.3(a)
Load class D400 in carriageways and medians; C250 within 0.5 m of the kerb; B125 in footpaths and cycle tracks (or the equivalent IS class) 9.11.2
Connection pipe At least 300 mm diameter; gradient giving at least 0.9 m/s at the inlet's design flow 6.6.6
Silt sump At least 300 mm deep below the outlet pipe invert, cleanable from the surface 6.6.7, 9.11.6

The intended layout of the annex is given in Tables 6A.2 to 6A.4.

Table 6A.2 — Register of standard inlet types (layout)

Type code Description Grate size or kerb opening (mm) Gutter depression (mm) Load class Standard drawing
______ ______ ______ ______ ______ ______
______ ______ ______ ______ ______ ______

Table 6A.3 — Capacity on grade (layout; one table per inlet type)

Cross slope Sx (m/m) Longitudinal slope SL (m/m) Gutter flow Q (L/s) Spread T (m) Clean intercepted flow (L/s) Design intercepted flow after clogging (L/s) Bypass flow (L/s)
______ ______ ______ ______ ______ ______ ______
______ ______ ______ ______ ______ ______ ______

Table 6A.4 — Capacity in a sag (layout; one table per inlet type)

Ponded depth at the inlet (mm) Clean capacity (L/s) Clogging factor (Table 6.5) Design capacity (L/s) Flow regime (weir, orifice or transition)
______ ______ ______ ______ ______
______ ______ ______ ______ ______

Annex 6B — Sediment yield for silt-trap sizing and calibration of the sediment allowance

Supports Clauses 6.7.4, 6.7.8, 6.13.3 and 6.13.10 of Chapter 6.

To be prepared. This annex will contain sediment yields for urban drains in Arunachal Pradesh, by land use and drain type, for sizing the silt traps of Clause 6.13.3, and a calibration of the sediment allowance of Clause 6.7.8 against measured silt depths. It needs desilting records (volume or mass removed per drain length and per catchment area, with dates), silt-depth surveys before and after the monsoon season, and catchment land-use and soil data (data and likely sources: desilting records of Itanagar Municipal Corporation and other urban local bodies, WRD records for channels, land cover from NRSC, soils from the Arunachal Pradesh soil survey and NBSS&LUP, rainfall from IMD). Until it is published, size each silt trap from the designer's stated estimate of the sediment expected between scheduled cleanings, based on the desilting records of the same drain or of similar drains in the same local body, and state the cleaning interval assumed; the interval shall not be longer than the yearly pre-monsoon desilting of Clause 6.13.10. Inlet silt sumps remain at least 300 mm deep (Clause 6.6.7), and the sediment allowance of Clause 6.7.8 applies unchanged.

The intended method is a simple volume balance, with every term to be stated in the design:

V_trap = Y · A · t_c

where V_trap is the sediment storage volume of the trap below its outlet invert (m³), Y is the sediment yield for the catchment's land use and drain type (m³/ha per year, from Table 6B.2 once published), A is the catchment area draining to the trap (ha), and t_c is the scheduled cleaning interval (years). The annex will state whether a safety margin is added.

Table 6B.1 — Sediment allowances already set by Chapter 6 (provisional, to be calibrated)

Element Sediment allowance at the invert Clause
Open and covered drains Greater of 75 mm and 10% of the clear internal depth 6.7.8(a)
Pipes of 600 mm diameter or more 5% of the internal diameter 6.7.8(b)
Pipes below 600 mm No allowance; minimum velocity of Clause 6.7.3(a) applies 6.7.8(c)
Drains and pipes that cannot reach the minimum velocity Allowance doubled; mechanical desilting access provided 6.7.4(b), (c)
Inlet silt sumps At least 300 mm below the outlet pipe invert 6.6.7

Table 6B.2 — Sediment yield by land use and drain type (layout)

Land use or catchment type Drain type Sediment yield Y (m³/ha per year) Bulk density (t/m³) Local body and records used Years of record
______ ______ ______ ______ ______ ______
______ ______ ______ ______ ______ ______

Table 6B.3 — Calibration of the sediment allowance (layout)

Drain or pipe ID Clear internal depth or diameter (mm) Allowance under Clause 6.7.8 (mm) Measured silt depth before pre-monsoon desilting (mm) Measured silt depth at the end of the monsoon (mm) Ratio of measured to allowance
______ ______ ______ ______ ______ ______
______ ______ ______ ______ ______ ______

Annex 6C — Standard drawings: covered roadside drain with removable covers, access chamber, inlet with silt sump

Supports Clauses 6.6, 6.7.6 to 6.7.10 and 6.13 of Chapter 6, and Clauses 9.11 and 9.12 of Chapter 9.

The drawings below are schematic standard drawings. They show only the dimensions that Chapter 6 and Chapter 9 set. Wall and slab thicknesses, reinforcement, concrete grade and cover, chamber plan sizes and frame details are to be confirmed in design: they come from the structural design (Clause 9.1.2) and the exposure class of Clause 9.13. Table 6C.1 lists the dimensions shown and their source clauses.

Covered roadside drain with removable covers Standard drawing: covered roadside drain with removable covers (not to scale) (a) Cross-section Property side Carriageway clear width ≥ 0.6 m clear depth ≥ 0.6 m freeboard to soffit (Table 6.7) Sediment allowance: greater of 75 mm and 10% of clear depth (6.7.8(a)) Removable cover panel, flush with footpath, recessed lifting points (6.13.2(a)) Slots in cover for footpath runoff (6.13.1(c)) Kerb opening at road level, ≥ 100 mm high, ≥ 1.0 m long, with silt sump (6.13.1(b), 9.11.4; Figure 6C.3) Wall and slab thickness, reinforcement, concrete grade and cover: to be confirmed in design (structural design; exposure class per Clause 9.13). Sealed joints next to sewers (6.13.7). (b) Requirements shown on this drawing Clear internal size ≥ 0.6 m × 0.6 m (6.7.6(c)) Removable panels at ≤ 10 m centres, ≥ 0.6 m long, full clear width (6.13.2(a)) Access chambers at ≤ 30 m centres and at every junction, bend, change of section; opening ≥ 0.6 m × 0.6 m (6.13.2(b)) Kerb inlets spacing by calculation, ≤ 30 m (6.6.4) Freeboard to soffit, Table 6.7; ≥ 150 mm Cover load class B125 footpath; C250 within 0.5 m of kerb (9.11.2) Utilities none along or through the flow area or freeboard (6.13.6) (c) Plan along the footpath (one 60 m length shown) ≤ 10 m ≤ 30 m between access chambers Access chamber Removable panel Kerb inlet

Figure 6C.1 — Standard drawing: covered roadside drain with removable covers, kerb inlets at road level, footpath slots, freeboard to the soffit and sediment allowance, with a plan of cover panels and access chambers along the footpath. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), Chapter 5, and IRC:SP:50-2013.

Access chamber on a covered drain Standard drawing: access and junction chamber on a covered drain (not to scale) (a) Plan at a junction (b) Section A–A Clear opening ≥ 600 × 600 mm (6.13.2(b), 9.12.3) internal width ≥ 2 × outgoing drain width (6.7.10(b)) Incoming drain enters at less than a right angle to the outgoing flow (6.7.10(b)) Chambers at every junction, bend and change of section, and at ≤ 30 m on straight runs (6.13.2(b)) A A ≥ 600 mm Cover rated for its location (9.11.2); hinged or locked (9.11.5); bolted or locked where the 1% HGL can rise above it (9.12.6) Outgoing invert below chamber floor: no standing water (6.7.10(b)) Ladder, if provided: corrosion- resistant, encapsulated (9.12.7) Designed for cleaning by suction, jetting or grab from the surface; no manual entry (9.12.7) Wall, slab and floor thickness, reinforcement and frame details: to be confirmed in design (Clause 9.1.2).

Figure 6C.2 — Standard drawing: access and junction chamber on a covered drain, with the clear opening, junction width, entry angle of the incoming drain, outgoing invert below the chamber floor, and cover requirements. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), §5.3.4 and Chapter 11.

Kerb inlet with silt sump Standard drawing: kerb inlet with silt sump (not to scale) (a) Section through the inlet Carriageway, cross slope Sx Gutter depression where practicable (6.6.1(b)); depth: to be confirmed in design Footpath Cover or grate at footpath level, hinged or locked (9.11.5); C250 within 0.5 m of kerb, D400 in carriageway (9.11.2) Kerb opening at road level (Clause 6.6.1(b)); see (b) Connection pipe ≥ 300 mm dia, gradient for ≥ 0.9 m/s at design flow (6.6.6) Silt sump ≥ 300 mm below outlet invert (6.6.7) Sump emptied from the surface by suction or grab machine (9.11.6) Chamber plan size, wall and slab thickness, reinforcement: to be confirmed in design. Size the chamber so the sump can be emptied by machine (9.11.6). (b) Elevation of kerb opening length ≥ 1.0 m (9.11.4) height ≥ 100 mm Kerb face / drain wall Road level Opening at road level (6.6.1(b), 9.11.4). Where a gutter grate is added (combination inlet): openings parallel to the direction of travel ≤ 25 mm (9.11.3); clogging factors of Table 6.5 apply to each part.

Figure 6C.3 — Standard drawing: kerb inlet at road level with silt sump, connection pipe and cover, and an elevation of the kerb opening. Original drawing for this Manual, adapted from CPHEEO, Manual on Storm Water Drainage Systems (2019), Figure 5.9, and FHWA, HEC-22 Urban Drainage Design Manual (4th ed., 2024).

Table 6C.1 — Dimensions on the standard drawings and their source clauses

Drawing Item Dimension or rule Clause
6C.1 Clear internal size of a covered public drain At least 0.6 m wide and 0.6 m deep 6.7.6(c)
6C.1 Freeboard to the cover soffit Table 6.7; not less than 150 mm for any roadside drain 6.7.9, 6.13.1(a)
6C.1 Sediment allowance Greater of 75 mm and 10% of clear depth 6.7.8(a)
6C.1 Removable cover panels At not more than 10 m centres; each at least 0.6 m long and spanning the full clear width; recessed lifting points; flush with the footpath 6.13.2(a)
6C.1 Footpath runoff Through slots or grated openings in the cover 6.13.1(c)
6C.1 Kerb inlets Openings in the drain wall at road level, each with a silt sump; spacing by calculation, not more than 30 m 6.13.1(b), 6.6.4
6C.1, 6C.2 Access chambers At every junction, bend and change of section, and at not more than 30 m centres on straight runs 6.13.2(b)
6C.2 Clear access opening At least 0.6 m × 0.6 m (600 mm) 6.13.2(b), 9.12.3
6C.2 Junction chamber Internal width at least twice the outgoing drain width; incoming drains at less than a right angle; outgoing invert below the chamber floor 6.7.10(b)
6C.2 Covers Load class for the location; hinged or locked; bolted or locked where the 1% AEP HGL can rise above the cover 9.11.2, 9.11.5, 9.12.6
6C.2 Cleaning By machine from the surface; ladders, where provided, corrosion-resistant and encapsulated 9.12.7
6C.3 Kerb opening At road level; clear height at least 100 mm; length at least 1.0 m 6.6.1(b), 9.11.4
6C.3 Silt sump At least 300 mm below the outlet pipe invert; emptied by suction or grab machine 6.6.7, 9.11.6
6C.3 Connection pipe At least 300 mm diameter; at least 0.9 m/s at the design flow 6.6.6
6C.3 Grate in a combination inlet Openings parallel to travel not wider than 25 mm; Table 6.5 clogging on each part 9.11.3, 6.6.3
All Wall and slab thickness, reinforcement, concrete grade and cover, chamber plan size, gutter depression depth To be confirmed in design 9.1.2, 9.13

Form 6-1 — Conveyance Design Report checklist

Supports Clause 6.15 of Chapter 6.

Draft form — Arunachal Pradesh Stormwater Design Manual, Draft v1.0. Not for statutory use.

Attach this checklist to the front of the Conveyance Design Report. For each item, enter Yes, No or Not applicable, and the drawing or page where it is shown.

Section A — Project

Table 6F.1 — Form 6-1, Section A: project

Field Entry
Project name and location ______
Local body, and Tier A or Tier B (Chapter 1) ______
Applicant ______
Designer (name and registration) ______
Total catchment area served (ha) ______
High-density area status for the 10% AEP minor system (Clause 6.4.4) ______
Within the coastal band of Clause 6.11.6 (Yes / No) ______
Date and revision ______

Section B — Contents required by Clause 6.15

Table 6F.2 — Form 6-1, Section B: contents required by Clause 6.15

No. Item Clause Provided (Yes / No / NA) Drawing or page
1 Catchment plan: sub-catchments, minor system, inlet locations and the 1% AEP major-system overland flow paths 6.3.2    
2 Land-use and road-class AEP adopted for each element, and the high-density area status Table 6.1, 6.4.4    
3 Design flows, with the rainfall sheet of Chapter 2 and the method of Chapter 3 6.3.4    
4 Gutter spread, depth and D·V checks for the minor, check and 1% events Tables 6.2, 6.3    
5 Inlet schedule: clean capacity, clogging factor, design capacity and bypass flow 6.6    
6 Pipe and drain design tables: n, velocity, sediment allowance and freeboard 6.7    
7 HGL profiles for the minor and check events, with the tailwater used 6.8    
8 Sag ponding levels, including the fully-blocked check 6.10    
9 Floor-level schedule for every building 6.11    
10 Culvert and crossing calculations (with Form 9-1) 6.12, Chapter 9    
11 Utilities-crossing schedule and access-opening layout for covered drains 6.13    

Section C — Design basis

Table 6F.3 — Form 6-1, Section C: design basis

Field Entry Clause
Minor-system design AEP adopted ______ Table 6.1
Road class(es) and design / check AEPs for road drainage and crossings ______ Table 6.1, 6.4.2
Rainfall source and climate factor applied ______ 6.3.4, Chapter 2
Method: Rational Method (catchment ≤ 16 ha, single element) or hydrograph method with routing ______ 6.3.4(a), (b)
Minimum time of concentration used (not less than 10 min) ______ 6.3.4(c)
Tailwater at the outfall for the HGL (MHWS + 0.3 m at tidal outfalls, or the receiving level) ______ 6.8.2
Any transfer of flow between natural catchments (none unless accepted under 6.3.5) ______ 6.3.5

Section D — Compliance checks

Table 6F.4 — Form 6-1, Section D: compliance checks

No. Check Limit Clause Complies (Yes / No / NA)
D1 Every inlet, sag, pipe, drain, culvert and storage element has a 1% AEP overland path Shown on plan 6.3.2  
D2 Major-system flow = 1% AEP peak less the clogged minor-system capacity Computed at each point 6.3.3  
D3 Spread in the minor event Table 6.2 6.5.2  
D4 Depth in the check and 1% events ≤ 150 mm at the crown; ≤ 350 mm at the deepest point Table 6.2  
D5 Flow hazard (D·V) by location Table 6.3 6.5.3  
D6 Inlet clogging factors applied Table 6.5 6.6.3  
D7 Inlet spacing on kerbed roads ≤ 30 m 6.6.4(a)  
D8 Sag inlet design capacity ≥ minor design flow arriving; flanking inlets where required — 6.6.5  
D9 Inlet connection pipes and silt sumps ≥ 300 mm dia, ≥ 0.9 m/s; sump ≥ 300 mm 6.6.6, 6.6.7  
D10 Manning's n not less than the minimum design values Table 6.6 6.7.2  
D11 Minimum velocity at the minor design flow 0.6 m/s drains; 0.9 m/s pipes 6.7.3(a)  
D12 Maximum velocity and Froude number 3.0 m/s lined drains and pipes; Fr ≤ 0.8 6.7.3(b), (d)  
D13 Where minimum velocity cannot be met: velocity reported, sediment allowance doubled, desilting access provided — 6.7.4  
D14 Pipes sized for pipe-full capacity, not the 0.95-depth peak — 6.7.5  
D15 Minimum sizes Pipes 300 mm (450 mm public mains); open drain bed 0.3 m; covered public drains 0.6 m × 0.6 m 6.7.6  
D16 Cover to pipes; flotation check where groundwater is within 1 m of the crown ≥ 0.6 m; ≥ 0.9 m under carriageways 6.7.7  
D17 Sediment allowance in capacity 6.7.8 values 6.7.8  
D18 Freeboard, including superelevation at bends Table 6.7 6.7.9  
D19 Bend radii and junction sumps 6.7.10 6.7.10  
D20 Manhole spacing on straight runs Table 6.8 6.7.11  
D21 HGL below inlet rims and manhole covers in the minor event ≥ 0.3 m 6.8.3  
D22 Manholes that can surcharge above ground: bolted or locked covers — 6.8.4  
D23 Soffits matched or outgoing soffit lower; outgoing invert not above the lowest incoming invert — 6.8.6  
D24 Gate and valve losses included in the HGL; non-return valves on private connections where required — 6.8.7, 6.8.8  
D25 Overland flow paths outside streets: width, tenure, no obstruction, continuous fall ≥ 1% top width + 0.5 m each side, ≥ 3.0 m 6.9.2  
D26 Compound walls across mapped flow paths: openings pass the 1% flow at 50% blockage — 6.9.3  
D27 Access strip along open drains with top width ≥ 2 m ≥ 3.5 m, linked to a road at ≤ 500 m 6.9.4  
D28 Drainage reserve where required: width, separate plot, no structures, markers, services, 2 m stability check Table 6.9 6.9.6–6.9.8  
D29 Sag ponding in the 1% event, overflow route, and fully-blocked check ≤ 350 mm at the deepest point 6.10.2, 6.10.3  
D30 Trapped sags and road underpasses 6.10.4, 6.10.5 6.10.4, 6.10.5  
D31 Floor levels ≥ 1% AEP level + 0.5 m; defaults of 6.11.3 where no level is computed 6.11.1–6.11.3  
D32 Basements and building services 6.11.4, 6.11.5 6.11.4, 6.11.5  
D33 Coastal band: floor ≥ 1% still-water level + 2 × SLA (+ wave set-up where applicable) + 0.5 m; no basement rooms or plant — 6.11.6  
D34 Culverts: design AEP, overtopping, 50% / 20% blockage check, minimum size ≥ 900 mm 6.12  
D35 Covered drains: removable panels and access chambers ≤ 10 m; ≤ 30 m 6.13.1, 6.13.2  
D36 Silt traps, screens with bypass and 50% blockage check — 6.13.3, 6.13.4  
D37 No building over drains; no utilities in the flow area or freeboard; existing crossings deducted with 50% blockage — 6.13.5, 6.13.6  
D38 No sewage connections; sealed joints next to sewers; edge protection on open drains deeper than 1.0 m — 6.13.7, 6.13.8  
D39 Outfalls: tailwater, flap gates or non-return valves below the 1% still-water level, outlet protection — 6.14  

Section E — Variances

Table 6F.5 — Form 6-1, Section E: variances

Clause Requirement not met Reason and proposed alternative Approved by and date
______ ______ ______ ______

Section F — Signatures

The report shall be prepared and signed by a registered professional, and the Professional Design Certificate (Form 10-3) attached (Clauses 10.6.1 and 10.6.3 of Chapter 10). Where a structure stands within 2 m of the edge of a drainage reserve, the stability design shall also be signed by a qualified structural engineer (Clause 6.9.8(f)).

Table 6F.6 — Form 6-1, Section F: signatures

Role Name Registration or empanelment no. Signature Date
Designer ______ ______ ______ ______
Structural engineer (Clause 6.9.8(f), where applicable) ______ ______ ______ ______

Draft form — Arunachal Pradesh Stormwater Design Manual, Draft v1.0.